Further information for ABB Automation AF16Z-40-00-21 contactor 24-60 VDC
General
Rated control supply voltage Us at AC 50HZ
60
Rated control supply voltage Us at AC 60HZ
60
Rated control supply voltage Us at DC
60
Voltage type for actuating
AC/DC
Rated operation current Ie at AC-1, 400 V
30
Rated operation current Ie at AC-3, 400 V
18
Rated operation power at AC-3, 400 V
7.5
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Screw connection
Number of normally closed contacts as main contact
0
Number of main contacts as normally open contact
4
Depth
77
Height
86
Operating voltage at AC 50 Hz
690
Operating voltage at AC 60 Hz
690
Width
45
Modular version
The 4-pole AF12Z contactors are designed for switching power circuits with slightly inductive, non-inductive loads or motors. They have an electronic coil interface that can implement a very wide control voltage. This means that even large control voltage fluctuations can be handled. The contactors with coil code -21 enable direct control via =24V DC 500mA PLC outputs and require a very low holding power of only 1.7W. AFZ contactors can withstand short voltage dips and voltage drops (according to SEMI F47-0706). All integrated or subsequently attached auxiliary break contacts are designed as mirror contacts in accordance with IEC60947-5-1 Appendix L. They also have built-in overvoltage protection and do not require any additional suppression elements. Other accessories such as timing elements, wiring aids and locking elements, etc., complete the range.