Further information for ABB Automation 1SAM350005R1007 motor protection switch MS132-2.5-HKF1-11
General
Overload release current setting
2.5
Adjustment range undelayed short-circuit release
31.3
Switch off technique
Thermomagnetic
Rated operating voltage
690
Rated permanent current Iu
2.5
Rated operation power at AC-3, 230 V
0.75
Rated operation power at AC-3, 400 V
0.75
Type of electrical connection of main circuit
Screw connection
Type of control element
Other
Device construction
Complete device in housing
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
100
Degree of protection (IP)
IP20
Height
90
Width
45
Depth
86.75
Power loss
5.4
With thermal protection
Phase failure sensitive
With integrated auxiliary switch
With integrated under voltage release
Motor protection switch MS132 with thermal and electromagnetic protection represents the compact and powerful series with high short-circuit breaking capacity for motor protection up to 15 kW (400 V) with a module width of 45 mm. The temperature-compensated device has a rotary handle operation with a clear switch position indicator I/TRIP/0. In addition, MS132 has a short-circuit indicator. The rotary handle can be locked directly in the 0 position using a padlock. Auxiliary, signal and short-circuit signaling contacts as well as undervoltage and shunt current releases can be installed without tools. MS132-HKF1-11 has a front-mounted auxiliary switch with 1NO/1NC contacts. 3-phase busbars for 65 A or 100 A and feed-in blocks for 25 mm² or 35 mm² allow several motor protection switches to be fed together. Protective housings and accessories for control cabinet and door installation complete the range. Atex certification allows the protection of motors in Ex areas, UL approval as >Self protected combination motor controller< expands the area of application in North America.