Further information for ABB Automation 1SAM350000R1008 MS132-4.0 motor protection switch
General
Overload release current setting
4
Adjustment range undelayed short-circuit release
50
Switch off technique
Thermomagnetic
Rated operating voltage
690
Rated permanent current Iu
4
Rated operation power at AC-3, 230 V
1.5
Rated operation power at AC-3, 400 V
1.5
Type of electrical connection of main circuit
Screw connection
Type of control element
Other
Device construction
Complete device in housing
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
100
Degree of protection (IP)
IP20
Height
90
Width
45
Depth
86.75
Power loss
5.4
With thermal protection
Phase failure sensitive
With integrated auxiliary switch
With integrated under voltage release
The MS132-4.0 motor protection switch from ABB is a compact, thermomagnetic switching device for motor protection in industrial applications. With a rated operational voltage of 690 V and a rated continuous current Iu of 4 A, it is designed for applications with low to medium power. The device type is a complete unit in an enclosure, featuring a rotary handle operation with clear switching position indicators (I/TRIP/0). The tripping technology combines thermal and electromagnetic protection, where the thermal protection detects motor overload and the electromagnetic protection responds to short circuits. The current setting of the overload tripping unit is 4 A, while the instantaneous short-circuit tripping unit has a setting range of 50 A. The protection class IP20 safeguards against finger contact and larger solid objects, but not against dust or water – therefore, application is intended within enclosed enclosures.
Applications
The MS132-4.0 is designed for motor protection in industrial plants, particularly in drive technology up to 15 kW at 400 V. It is suitable for applications requiring reliable protection against overload and short circuit. The phase failure sensitivity enables detection of missing phases in the power supply network, which is important for three-phase motors to avoid damage from uneven loading. The approval as a >Self protected combination motor cotroller< extends the application range in North America, with UL certification enabling use in specific electrical installations. ATEX certification is also available, allowing use in hazardous areas, although not specified for this particular item.
Functions and Equipment in Detail
The device features a temperature-compensated tripping function that stabilizes the thermal response independently of ambient temperatures. The rotary handle operation is equipped with a clear switching position indicator, visually showing the operating state (I = on, TRIP = tripped, 0 = off). The rotary handle can be locked in the 0 position with a padlock, enabling secure disconnection. A short-circuit indicator signals the cause of tripping, simplifying fault diagnosis. The main circuit connection is via screw terminals, with a pole count of 3. The rated short-circuit breaking capacity Icu at 400 V, AC is 100 kA, ensuring high safety during short-circuit events.
Technology Explained Simply
The thermomagnetic tripping technology combines two protection principles: the thermal part responds to continuous overload by triggering a mechanism through thermal expansion. The magnetic part reacts immediately to high current surges, such as those occurring during short circuits. The current setting of 4 A means the protection trips at a continuous current flow of 4 A, while the short-circuit tripping unit responds instantly at 50 A. The power loss is 5.4 W, describing the heat generation during operation. The rated operational power at AC-3 is 1.5 kW at 230 V and 400 V, defining the performance capability for motor drives.
Compatibility and Accessories
Various accessories are available for this motor protection switch, extending its functionality. These include non-coded latching mechanisms (MSMNO) and latching mechanisms with screws (MSMN), suitable for mechanical interlocking or connection with other switches. These components are designed for the MS 116, MS 225/325 series. Mounting of auxiliary, signaling, and short-circuit alarm contacts, as well as undervoltage and operating current tripping units, is possible without tools, simplifying installation and maintenance. For common power supply to multiple motor protection switches, 3-phase busbars for 65 A or 100 A, and feed blocks for 25 mm² or 35 mm² are available.
Mounting and Installation
Mounting is carried out in enclosures or on doors, with the device type being a complete unit in an enclosure. The screw terminal connection allows for a secure and stable connection. The module width is 45 mm, facilitating placement in standard switchboards. Dimensions are 90 mm (height), 45 mm (width), and 86.75 mm (depth). Installation requires no special tools for mounting auxiliary or signaling contacts, simplifying maintenance and expansion.
Operational Advantages
The MS132-4.0 provides reliable motor protection through the combination of thermal and magnetic tripping mechanisms. The temperature-compensated tripping ensures consistent responsiveness regardless of ambient conditions. The clear switching position indicator and short-circuit indicator simplify diagnosis and maintenance. The ability to lock the rotary handle with a padlock increases safety during maintenance work. The high rated short-circuit breaking capacity of 100 kA at 400 V, AC ensures safe disconnection during short-circuit events. Compatibility with accessories such as latching mechanisms and feed blocks enables flexible integration into existing switchgear systems.