Further information for ABB Automation 1SAM340000R1012 MS132-12T transformer protection switch primary side
General
Rated permanent current Iu
12
Rated voltage
690
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100
Overload release current setting
12
Adjustment range undelayed short-circuit release
240
Type of electrical connection of main circuit
Screw connection
Device construction
Complete device in housing
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Position of connection for main current circuit
Front side
Type of control element
Turn button
Degree of protection (IP)
IP20
Power loss
6
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With switched-off indicator
Complete device with protection unit
Motor drive integrated
Motor drive optional
With integrated under voltage release
Transformer circuit breaker MS132-T with thermal and electromagnetic protection represents the compact and powerful series with high short-circuit breaking capacity for transformer protection up to 25 A with a module width of 45 mm. With this device, the primary-side transformer rated current is thermally monitored by setting on the current scale. The short-circuit is triggered when 20 times the device rated current occurs. The temperature-compensated device has a rotary handle operation with a clear switch position indicator I/TRIP/0. In addition, MS132-T has a short-circuit indicator. The rotary handle can be directly locked in the 0 position using a padlock. Auxiliary, signal and short-circuit signaling contacts as well as undervoltage and shunt current releases can be installed without tools. 1-phase feed-in blocks up to 25 mm² and phase connectors support the wiring of 1-phase transformers.