Further information for ABB Automation 1SAM250000R1011 motor protection switch MS116-16 10–16 A
General
Overload release current setting
16
Adjustment range undelayed short-circuit release
240
Switch off technique
Thermomagnetic
Rated operating voltage
690
Rated permanent current Iu
16
Rated operation power at AC-3, 230 V
7.5
Rated operation power at AC-3, 400 V
7.5
Type of electrical connection of main circuit
Screw connection
Type of control element
Other
Device construction
Complete device in housing
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
16
Degree of protection (IP)
IP20
Height
90
Width
45
Depth
85.6
Power loss
8.4
With thermal protection
Phase failure sensitive
With integrated auxiliary switch
With integrated under voltage release
The MS116-16 motor protection switch from ABB is a compact switching device for motor protection in industrial applications. It is designed for use in enclosures and provides thermal and electromagnetic protection to safeguard motors against overload and short-circuit. The MS116 series features a module width of 45 mm, enabling economical and space-saving installation in standard switchgear. The device is temperature-compensated to ensure reliable tripping regardless of ambient temperatures.
Applications
The motor protection switch is designed for use in electrical installations with a rated operating voltage up to 690 V. It protects motors up to a power of 15 kW at 400 V operating voltage. Typical applications include industrial automation, production plants, or installations with electric drives, where safe and reliable disconnection is required in case of faults. The IP20 protection rating makes the device suitable for use in enclosed enclosures, where direct contact with moving parts or foreign objects is not possible.
Functions and Equipment in Detail
The switch features a rotary handle with a clear ON/OFF position indicator, visually displaying the operating status. The rotary handle can be locked in the OFF position using a locking device to prevent accidental switching on. The tripping mechanism is thermomagnetic, with the thermal tripping element responsible for overload protection and the magnetic tripping element for short-circuit protection. The overload tripping current setting is 16 A, while the instantaneous short-circuit tripping range extends up to 240 A. The device is phase-loss sensitive, meaning it reacts to a phase failure and disconnects the motor to prevent damage.
Technology Explained Simply
The thermal protection function is based on a bimetal element that triggers the switch by thermal expansion under sustained overload conditions. The magnetic protection function responds immediately to high current surges, such as those occurring during short circuits. The rated continuous current Iu is 16 A, indicating the maximum current the device can carry continuously. The rated short-circuit breaking capacity Icu at 400 V, AC is 16 kA, describing the maximum breaking capacity under short-circuit conditions. The power loss is 8.4 W, indicating the electrical power dissipated as heat in the device.
Compatibility and Accessories
Various accessories are available for this motor protection switch to extend its functionality. These include interlock actuators with screw (MSMN) and without coding (MSMNO) for mechanical interlocking of multiple switches, as well as padlocks with two keys (SA2 GJF1101903R0002) for additional security. The main circuit connection is via screw terminals, ensuring a robust and secure connection. The number of poles is 3, required for use in three-phase networks. The device type is a complete unit in an enclosure, designed for direct installation in enclosures.
Mounting and Installation
Mounting is carried out in standard switchgear, with the module width of 45 mm allowing easy integration into DIN rails. The connection terminals are designed for screw connections, ensuring a secure and durable connection. Installation does not require special tools, as auxiliary and signal contacts, as well as undervoltage and operating current release mechanisms, can be installed without tools. The use of 3-phase rails for 65 A or 100 A, as well as feed blocks for 25 mm² or 35 mm², enables common feeding of multiple motor protection switches, simplifying planning and installation.
a motor protection switch, which thermally and electromagnetically protects, with IP20 protection rating and thermomagnetic tripping technology. The rated operating voltage is 690 V, the rated continuous current is 16 A. The device is phase-loss sensitive and designed for use in industrial enclosures. The module width of 45 mm enables compact installation.
Advantages in Operation
The motor protection switch provides reliable protection for electric motors, minimizing downtime and damage to drive components. The clear position indicator and the ability to lock the rotary handle enhance safety during maintenance work. The modular design and compatibility with accessories such as interlock actuators and padlocks expand the range of applications. The thermal compensation ensures consistent protection regardless of environmental influences. The rated operational power is 7.5 kW at AC-3 and 230 V as well as 400 V, describing the device’s performance under various operating conditions.