ABB 1SAM250000R1010, EAN: 4013614320330

ABB Automation 1SAM250000R1010 motor protection switch MS116-10 6,3–10 A

Industrial Material > Control devices / Pilot devices > Motor protection switch

ABB Automation 1SAM250000R1010 motor protection switch MS116-10 6,3–10 A

Lieske Part No. 854811
Mfg Part No 1SAM250000R1010
EAN-Code 4013614320330
Manufacturer ABB
Here only 109,25 EUR
130,01 EUR incl. VAT

Further information for ABB Automation 1SAM250000R1010 motor protection switch MS116-10 6,3–10 A

General
Overload release current setting10
Adjustment range undelayed short-circuit release150
Switch off techniqueThermomagnetic
Rated operating voltage690
Rated permanent current Iu10
Rated operation power at AC-3, 230 V4
Rated operation power at AC-3, 400 V4
Type of electrical connection of main circuitScrew connection
Type of control elementOther
Device constructionComplete device in housing
Number of poles3
Rated short-circuit breaking capacity lcu at 400 V, AC75
Degree of protection (IP)IP20
Height90
Width45
Depth85.6
Power loss7.2
With thermal protectionyes
Phase failure sensitiveyes
With integrated auxiliary switchno
With integrated under voltage releaseno
The MS116-10 motor protection switch from ABB is a compact switching system for electrical protection of motors in industrial applications. It is designed for use in installations with a rated operational voltage up to 690 V and provides both thermal and electromagnetic protection, implemented via a thermomagnetic tripping technology. The device is constructed as a complete unit in an enclosure, with main current circuits connected via screw terminals. The number of poles is 3, enabling use in three-phase installations. The rated continuous current Iu is 10 A, with the overload tripping unit set at 10 A. The instantaneous short-circuit tripping unit has an adjustable range of 150, ensuring rapid response under short-circuit conditions. The protection rating IP20 safeguards against finger contact and solid foreign objects, but not against water or dust – therefore, application is limited to enclosed enclosures. The rated short-circuit breaking capacity Icu is 75 kA at 400 V, AC, ensuring suitability for medium industrial installations. The power loss is 7.2 W.

Applications

The MS116-10 motor protection switch is suitable for motor protection in installations up to 15 kW at 400 V. It is used in industrial environments where a reliable and compact protection solution for electric motors is required. The module width of 45 mm enables space-saving installation in enclosures. The temperature-compensated design ensures consistent protection performance regardless of ambient temperatures, which is particularly important in environments with varying operating conditions.

Functions and Equipment in Detail

The device features a rotary handle operation with a clear switching position indicator I/0, visually displaying the operating status. The rotary handle can be locked in the 0 position using a locking device, preventing unintentional operation. The actuator design is defined as other, indicating a specific, non-standard form. Auxiliary and signal contacts, as well as undervoltage and load current tripping units, can be installed without tools, simplifying installation and maintenance. The integrated thermal protection function provides overload protection based on heat development within the device. Phase failure sensitivity detects missing phases in the circuit and triggers tripping upon detection, protecting the motor from damage.

Technology Explained Simply

The thermomagnetic tripping technology combines two protection principles: thermal protection, which is based on heat generation during overload, and electromagnetic protection, which responds to sudden current surges such as short circuits. The temperature-compensated design ensures that the protection function remains constant even with varying ambient temperatures. The rated operational power is 4 kW at AC-3, 230 V, and 4 kW at AC-3, 400 V, describing the device’s performance in typical application scenarios. The IP20 protection rating is suitable for use in enclosed enclosures, as it does not provide water or dust tightness.

Compatibility and Accessories

Various accessories are available for this motor protection switch, extending its functionality. These include a padlock with 2 keys (SA2 GJF1101903R0002), enabling additional securing of the 0 position. Additionally, linkages are available, such as the MSMN linkage with screw for MS 116/MS 225/325 and the MSMNO linkage without coding with screw for MS 116/MS 225/325. These allow mechanical interlocking with other switches or operating elements. The use of 3-phase rails for 65 A or 100 A, as well as feed blocks for 25 mm² or 35 mm², enables common feeding of multiple motor protection switches, simplifying installation in larger systems. Protective enclosures and accessories for enclosure and door mounting complement the range and allow flexible installation.

Installation and Mounting

Mounting is performed via screw terminals in the main current circuit. The rotary handle operation is designed for easy use, and the I/0 switching position indicator allows for quick visual inspection. The locking device for the 0 position can be used to secure against unintentional operation. Installation of auxiliary and signal contacts, as well as undervoltage and load current tripping units, is tool-free, accelerating the installation process. The module width of 45 mm enables space-saving installation in standard enclosures.

Operational Advantages

The MS116-10 motor protection switch provides reliable protection for motors up to 15 kW at 400 V. The thermomagnetic tripping technology ensures protection against overload and short circuit. The temperature-compensated design ensures consistent protection performance regardless of ambient temperatures. Tool-free installation of additional components reduces installation time. The use of 3-phase rails and feed blocks enables flexible and efficient integration into larger installations. The IP20 protection rating is suitable for use in enclosed enclosures, securing application in industrial environments.

Rated operational voltage, thermomagnetic tripping technology, thermal protection, phase failure sensitivity, IP20, module width 45 mm are the key features determining the functionality and suitability of the device.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/854811
qrcode für ABB Automation 1SAM250000R1010 motor protection switch MS116-10 6,3–10 A