Further information for ABB Automation 1SAM250000R1005 motor protection switch 0.63–1 A
General
Overload release current setting
1
Adjustment range undelayed short-circuit release
12.5
Switch off technique
Thermomagnetic
Rated operating voltage
690
Rated permanent current Iu
1
Rated operation power at AC-3, 230 V
0.25
Rated operation power at AC-3, 400 V
0.25
Type of electrical connection of main circuit
Screw connection
Type of control element
Other
Device construction
Complete device in housing
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
100
Degree of protection (IP)
IP20
Height
90
Width
45
Depth
85.6
Power loss
4.8
With thermal protection
Phase failure sensitive
With integrated auxiliary switch
With integrated under voltage release
The MS116-1.0 motor protection switch from ABB is a compact switching device for electrical protection of motors in industrial applications. It is part of the cost-effective MS116 series, designed for motor protection applications up to 15 kW at 400 V. The device has a module width of 45 mm and is designed for installation in enclosures. The version is a complete unit in an enclosure with screw connection in the main current circuit. The protection function is based on a thermomagnetic tripping technology, providing both thermal and electromagnetic protection. The thermal protection is temperature-compensated to ensure reliable operation at different ambient temperatures.
Motor protection switch with thermally-magnetic tripping technology provides protection against overload and short circuit. The current setting of the overload tripping unit is 1 A, with the instantaneous short-circuit tripping unit setting at 12.5. The rated operational voltage is 690 V, and the rated continuous current Iu is specified as 1 A. The rated operational power at AC-3 is 0.25 kW at both 230 V and 400 V. The rated short-circuit breaking capacity Icu at 400 V, AC, is 100 kA. The protection class IP20 safeguards against finger contact and solid foreign objects, but is not suitable for outdoor use or in damp environments.
Applications include protection functions for electric motors in industrial plants, particularly in drive technology, pumps, fans, and conveyor systems. The device is phase-loss sensitive, meaning it reacts to the failure of one phase in a three-phase network and switches off the motor to prevent damage. Operation is via a rotary handle with clear switching position indicators I/0, which can be locked in the 0 position using a locking device. This enables safe disconnection and prevents unintended re-energization.
Functions and equipment in detail include the ability to mount auxiliary and signal contacts, as well as undervoltage and current tripping units without tools. These expansion options allow flexible adaptation to specific requirements in the circuit diagram. The power loss is 4.8 W, which is relevant for heat generation during operation. The dimensions of the device are 90 mm (height), 45 mm (width), and 85.6 mm (depth). The number of poles is 3, required for use in three-phase systems.
Compatibility and accessories include compatible actuators such as the MSMN with screw for MS 116/MS 225/325 and the MSMNO without coding. These elements enable secure and tool-free mounting and locking. Additionally, a padlock with two keys is available to support the locking function. The series also offers 3-phase rails for 65 A and 100 A, as well as feed blocks for 25 mm² and 35 mm², enabling common feeding of multiple motor protection switches. Protection enclosures and accessories for enclosure and door mounting complete the range.
Mounting and installation take place in standard switchboards or enclosures. The screw connection in the main current circuit enables a secure and firm connection. Mounting typically occurs on a rail, with the device dimensions allowing placement in standard switchboards. The connection terminals are designed for use with cables of corresponding cross-sections.
Operational advantages lie in the combination of compact design, cost-effective execution, and high reliability. The thermal compensation ensures stable operation regardless of ambient temperature. The clear switching position indication and locking capability increase operational safety. The ability to mount additional contacts and tripping units without tools reduces installation time and increases flexibility in system design. The series is designed for use in industrial environments where reliable and low-maintenance protection functions are required.