Further information for ABB Automation 1SAM250000R1003 motor protection switch MS116-0.4
General
Overload release current setting
0.4
Adjustment range undelayed short-circuit release
5
Switch off technique
Thermomagnetic
Rated operating voltage
690
Rated permanent current Iu
0.4
Rated operation power at AC-3, 230 V
0.09
Rated operation power at AC-3, 400 V
0.09
Type of electrical connection of main circuit
Screw connection
Type of control element
Other
Device construction
Complete device in housing
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
100
Degree of protection (IP)
IP20
Height
90
Width
45
Depth
85.6
Power loss
5.1
With thermal protection
Phase failure sensitive
With integrated auxiliary switch
With integrated under voltage release
The MS116-0.4 motor protection switch from ABB is a compact switching system for electrical protection of motors with a rated continuous current of 0.4 A. It provides protection against overload and short-circuit during the operation of electric motors, particularly in industrial applications with an operating voltage up to 690 V. The device is part of the cost-effective MS116 series, designed for motor protection applications up to 15 kW at 400 V. The module width is 45 mm, enabling efficient space utilisation in enclosures.
Motor protection switch with thermal-magnetic tripping technology ensures reliable response to thermal overloads as well as sudden, high current surges. The thermal protection is temperature-compensated to ensure consistent protection regardless of ambient temperatures. The current setting of the overload tripping unit is 0.4 A, with the instantaneous short-circuit tripping unit having a 5-fold setting range. This allows precise adjustment to the specific requirements of the motor being protected.
Phase failure sensitivity is integrated, enabling the switch to react to the failure of any one of the three phases in a three-phase network and disconnect the motor to prevent damage from unbalanced loading. The switching position is indicated by a rotary handle with clear markings for I" (On) and "0 cm ( 0 inch ) (Off). The rotary handle can be locked in the "0 position using a locking device, preventing unintended operation and enhancing safety.
Protection class IP20 means the device is protected against contact with fingers and against solid foreign objects up to 12.5 mm in size. It is not intended for outdoor use or in damp environments. The main circuit connection is made via screw terminals, ensuring a secure and mechanically stable connection. The number of poles is 3, typical for use in three-phase installations.
The rated operational power at AC-3 is 0.09 kW at 230 V and 400 V, describing the device’s performance capability with typical motor drives. The rated short-circuit breaking capacity Icu is 100 kA at 400 V, highlighting the switch’s ability to interrupt high short-circuit currents. The power loss is 5.1 W, describing the thermal load on the device during operation.
Compatibility and accessories include various expansion options. Suitable accessories include non-coded lugs (MSMNO) and screw-type lugs (MSMN) for the MS 116 and MS 225/325 series, as well as padlocks with two keys (SA2 GJF1101903R0002). These components enable flexible integration into existing control systems. The ability to install auxiliary and signal contacts, as well as undervoltage and operational current tripping units without tools, increases installation flexibility. Three-phase rails for 65 A and 100 A, as well as feed blocks for 25 mm² and 35 mm², support the common feeding of multiple motor protection switches, simplifying installation in larger systems.
Mounting and installation are carried out in enclosures or on doors, with the device supplied as a complete unit in housing. The screw terminal connection ensures a secure and durable connection. The module width of 45 mm and dimensions of 90 mm (height), 45 mm (width), and 85.6 mm (depth) are designed for standard control panels. The device construction as a complete unit in housing offers an integrated, maintenance-friendly solution.
Operational advantages lie in the combination of compact design, high protection function, and easy handling. The temperature-compensated tripping ensures consistent protection, phase failure sensitivity prevents motor damage, and the locking capability enhances operational safety. The ability to install accessories without tools reduces installation time and maintenance effort. The device is designed for use in industrial environments where reliability and safety are paramount.