Further information for ABB Automation 1SAM250000R1002 motor protection switch MS116-0.25 16-25A
General
Overload release current setting
0.25
Adjustment range undelayed short-circuit release
3.1
Switch off technique
Thermomagnetic
Rated operating voltage
690
Rated permanent current Iu
0.25
Rated operation power at AC-3, 230 V
0.06
Rated operation power at AC-3, 400 V
0.06
Type of electrical connection of main circuit
Screw connection
Type of control element
Other
Device construction
Complete device in housing
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
100
Degree of protection (IP)
IP20
Height
90
Width
45
Depth
85.6
Power loss
4.8
With thermal protection
Phase failure sensitive
With integrated auxiliary switch
With integrated under voltage release
The MS116-0.25 motor protection switch from ABB is a compact switching device for electrical motor protection in industrial applications. It is part of the cost-effective MS116 series, designed for motor protection applications up to 15 kW at 400 V. The device has a module width of 45 mm and is designed for use in enclosures. The protection function is achieved through a thermomagnetic tripping technology, providing both thermal and electromagnetic protection. The thermal protection function is temperature-compensated to ensure reliable overload protection at different ambient temperatures.
Applications
The motor protection switch is intended for use in industrial plants, particularly in drive technology, where safe and reliable motor disconnection is required in case of overload or short circuit. It is suitable for applications with a rated operational voltage up to 690 V and a rated continuous current of 0.25 A. The protection rating IP20 makes the device suitable for use in enclosed enclosures, where mechanical damage and contact with hazardous parts must be avoided.
Functions and Equipment in Detail
The device features a rotary handle operation with a clear switching position indicator I/0, visually showing the operating status. The rotary handle can be locked in the 0-position using a locking device to prevent unintentional switching on. The overload tripping units are set at 0.25 A, while the instantaneous short-circuit tripping unit has an adjustable range of 3.1. The phase failure sensitivity ensures that the motor is switched off in case of a phase failure to prevent damage.
Technology Explained Simply
The thermomagnetic tripping technology combines a thermal and an electromagnetic tripping unit. The thermal part responds to sustained overloads by triggering the switch through thermal expansion. The electromagnetic part responds to sudden, high current surges such as short circuits and trips immediately. The rated short-circuit breaking capacity Icu is 100 kA at 400 V, highlighting the device's ability to safely interrupt high short-circuit currents. The power loss is 4.8 W, describing the thermal load on the device during operation.
Compatibility and Accessories
Various accessories are available for this motor protection switch to extend its functionality. These include cam levers with and without coding (MSMN, MSMNO) for mechanical interlocking of multiple switches, as well as padlocks with two keys (SA2 GJF1101903R0002), enabling additional securing of the 0-position. These components can be installed without tools, simplifying mounting and maintenance. The main circuit connection is made via screw terminals, with feed blocks for 25 mm² and 35 mm², as well as 3-phase rails for 65 A and 100 A, enabling common feeding of multiple switches.
Mounting and Installation
The motor protection switch is supplied as a complete unit in its housing and is intended for installation in enclosures. Mounting is done via screw terminals, supporting connection cross-sections up to 35 mm². The device design allows for easy integration into existing control systems. The connection options and use of rails and feed blocks facilitate the parallel installation of multiple switches in an enclosure.
Advantages in Operation
The motor protection switch provides reliable motor protection with low energy consumption and a compact design. The clear switching position indicator and the ability to lock in the 0-position increase operational safety. The thermal compensation ensures consistent protection regardless of ambient temperature. The possibility to install auxiliary and signaling contacts, as well as undervoltage and operational current tripping units without tools, reduces installation time and simplifies maintenance. The protection rating IP20 ensures sufficient protection against contact with hazardous parts and mechanical damage within the enclosure area.