Further information for Walther-Werke WAV0179R1
WALTHER connection distribution cabinet
Connected load: 55kVA
according to IEC61439-4
and DIN/VDE 43868/1
Housing (H16) made of electrolytically galvanized sheet steel
with heavy metal-free plastic coating
Color: RAL 2004 -pure orange-
with single door, spring latch for padlock
and recessed handle
with crane eyes and side handles
including hot-dip galvanized base frame with eyelets for ground nails
Installations up to and including RCD circuit breaker in the insulating housing
Protection class: IP 44
Measuring device Protection class: IP 54
Size approx.: 974 x 803 x 360mm / HBT
+ base frame height approx.: 323mm
Connection:
1 NH00 fuse switch disconnector 100A
with U-clamp terminals 10-50qmm
Measurement:
1 DS meter space without meter according to DIN 43870/2
outlet / Protection:
1 circuit breaker 3P 80A
with thermal-magnetic release
1 RCD circuit breaker 4P 63A/300mA -B-
1 CEE panel box 63A 5P 400V 6h
with miniature circuit breaker (MCB) 3P 50A -D-
1 RCD circuit breaker 4P 63A/30mA -B-
with miniature circuit breaker (MCB) 3P 50A -C-
2 CEE panel boxes 32A 5P 400V 6h
each with 1 miniature circuit breaker (MCB) 3P 32A -C-
3 CEE panel boxes 16A 5P 400V 6h
each with 1 miniature circuit breaker (MCB) 3P 16A -C-
6 earthed sockets 16A 2P 230V
each with 1 Miniature circuit breaker (MCB) 1P 16A -C-