Further information for Walther-Werke WAP0430 - Walther AP distributor stainless steel
WALTHER surface-mounted distributor
Connected load: 69kVA
Housing (H08-special) made of stainless steel (W1.4301) -bright/brushed-
with 4 wall mounting lugs -outside-
with single door and 3-point bar lock and swivel lever
with profile half cylinder, locking G2123
Installation up to and including RCD circuit breaker in the insulating housing
Protection class: IP 44
Size approx.: 974 x 669 x 360mm / HBT
Connection:
1 NH00 fuse switch disconnector 100A
with U-clamp 10-50qmm
Outlet / protection:
1 RCD circuit breaker 4P 63A/300mA -A-
1 CEE surface-mounted box 63A 5P 400V 6h
with fuse element 3P 63A (E33)
1 RCD circuit breaker 4P 63A/30mA -A-
with fuse element 3P 63A (E33)
2 CEE wall sockets 32A 5P 400V 6h each
with 1 circuit breaker (MCB) 3P 32A -C-
2 CEE wall sockets 16A 5P 400V 6h
each with 1 circuit breaker (MCB) 3P 16A -C-
1 RCD circuit breaker 4P 40A/30mA -A-
6 earthed sockets 16A 2P 230V
each with 1 circuit breaker (MCB) 1P 16A -C-