| General |
| Conductor diameter | 0,8 mm |
| Loop conductor resistance | 73,2 Ohm/km |
| Insulation resistance | 100 MΩ·km |
| Capacitive coupling | 200 pF/100 m |
| Operating capacity at 800 Hz | 100 nF/km |
| Test voltage core/core | 500 V |
| Operating peak voltage | 225 V |
| Temperature range in motion | -5 to +50 °C |
| Temperature range stationary | -30 to +70 °C |
| Bending radius | 7,5 x cable diameter |
| Wire insulation | YI3 according to DIN VDE |
| Pair identification | Siematic colour code |
| Screening | plastic-laminated aluminium foil with Cu-braid |
| Outer sheath | Blue |
The VOKA installation cable JE-Y (ST)Y 2 X 2 X 0,8 BL is a
telecommunications cable for the transmission of signals and measurement values in symmetrical circuits of control and regulation technology as well as in data and process computing systems. It is intended for fixed installation in dry and damp rooms, both in and under plaster, as well as on exterior walls of buildings. The blue outer sheath identifies the cable as suitable for
intrinsically safe systems, which plays an important role in industrial automation technology. The cable is not approved for high-voltage installation purposes or for direct earth burial.
Applications
This cable is used in systems where the transmission of control and regulation information must be secure and free from interference. Examples include building automation systems, industrial process control technology, measurement and monitoring systems, and data communication in closed networks. Installation is carried out indoors, on walls or in shafts, with routing under plaster or in cable ducts being common. Use on exterior walls requires additional mechanical and weather-resistant protective installation, as the cable is not designed for direct outdoor exposure.
Functions and Features in Detail
The cable consists of four pairs, each pair made up of two bare, solid copper conductors with a diameter of 0.8 mm. The conductors are insulated with PVC (YI3 according to DIN VDE) and marked according to the Siematic colour code, enabling clear identification of conductors within the network. The conductors are twisted into pairs with optimal lay lengths to minimize electromagnetic interference. The four pairs are bundled together and then twisted in layers to ensure a stable structure.
Technology Explained Simply
The
shielding is provided by a plastic-laminated aluminium foil with a bare copper drain wire. This construction protects signals from external electromagnetic interference and prevents signal radiation from the cable, which is important for signal integrity in sensitive installations. The
rated peak voltage is 225 V, indicating the maximum voltage the cable can safely transmit under operating conditions. The
loop resistance of the conductor is limited to a maximum of 73.2 Ohm/km, enabling signal transmission over long distances without excessive attenuation. The
insulation resistance is at least 100 MΩ·km, ensuring high insulation quality and low failure susceptibility. The
capacitive coupling is limited to a maximum of 200 pF/100 m to minimize signal coupling between conductors. The
operating capacitance at 800 Hz is a maximum of 100 nF/km, defining the electrical characteristics for data transmission in the frequency range.
Compatibility and Accessories
The cable is designed for use in systems based on symmetrical circuits, as commonly used in control and regulation technology. It is compatible with standard cable connectors and plugs designed for telecommunications cables with a 0.8 mm conductor diameter. The use of appropriate connection elements is necessary to meet electrical and mechanical requirements.
Installation and Mounting
Installation is carried out by fixed routing indoors, typically under plaster, in cable ducts, or on walls. When routing on exterior walls, additional mechanical and weather-resistant protective installation is required, as the cable is not designed for direct outdoor exposure. The
bending radius is 7.5 times the cable diameter, which must be considered during installation to avoid damage. The
temperature ranges are between -5 °C and +50 °C for moving installations and between -30 °C and +70 °C for stationary installations, enabling broad application in various environments.
Operational Advantages
The cable construction with shielding and optimized twisting ensures high signal quality and low interference susceptibility. The use of bare, solid copper conductors guarantees high electrical conductivity. The PVC insulation provides good mechanical and electrical insulation. The blue colour of the sheath identifies the cable as suitable for intrinsically safe systems, enabling clear identification in industrial automation technology. Installation indoors and on exterior walls expands the range of applications, although mechanical protective installation is required for outdoor use.