SM 323 - Digital in-/output
8x DI
8x DO
DC 24 V
1 A
For 20 pole front connector
SM 323 (323-1BH01)
Technical Data
Order no.: 323-1BH01
Type: SM 323
General Information:
- Note: -
- Features: 8x DI, 8x DO, DC 24 V, 1 A, for 20-pin front connector
- SPEED-Bus: no
Current Consumption/Power Loss:
- Current consumption from backplane bus: 70 mA
- Power loss: 4 W
Technical Data Digital Inputs:
- Number of inputs: 8
- Cable length, shielded: 1000 m
- Cable length, unshielded: 600 m
- Rated load voltage: DC 24 V
- Current consumption from load voltage L+ (without load): 15 mA
- Rated value: DC 20.4...28.8 V
- Input voltage for signal 0: DC 0...5 V
- Input voltage for signal 1: DC 15...28.8 V
- Input voltage hysteresis: -
- Signal logic input: Sinking input
- Frequency range: -
- Input resistance: -
- Input current for signal 1: 7 mA
- Connection of two-wire BEROs possible: yes
- Max. permissible BERO quiescent current: 1.5 mA
- Input delay of 0 to 1: 3 ms
- Input delay of 1 to 0: 3 ms
- Input filter delay: -
- Number of simultaneously utilizable inputs in horizontal configuration: 8
- Number of simultaneously utilizable inputs in vertical configuration: 8
- Input characteristic curve: IEC 61131-2, type 1
- Initial data size: 1 Byte
Technical Data Digital Outputs:
- Number of outputs: 8
- Cable length, shielded: 1000 m
- Cable length, unshielded: 600 m
- Rated load voltage: DC 24 V
- Reverse polarity protection of rated load voltage: yes
- Current consumption from load voltage L+ (without load): 15 mA
- Output current at signal 1, rated value: 1 A
- Signal logic output: Sourcing output
- Output delay of 0 to 1: 150 µs
- Output delay of 1 to 0: 100 µs
- Minimum load current: -
- Lamp load: 5 W
- Parallel switching of outputs for redundant control of a load: possible (only within the group)
- Parallel switching of outputs for increased power: not possible
- Actuation of digital input: yes
- Switching frequency with resistive load, max.: 1000 Hz
- Switching frequency with inductive load, max.: 0.5 Hz
- Switching frequency on lamp load, max.: 10 Hz
- Internal limitation of inductive shut-off voltage: L+ (-52 V)
- Short-circuit protection of output: yes, electronic
- Trigger level: 1.5 A
- Number of operating cycles of relay outputs: -
- Switching capacity of contacts: -
- Output data size: 1 Byte
Status Information, Alarms, Diagnostics:
- Status display: green LED per channel
- Interrupts: no
- Process alarm: no
- Diagnostic interrupt: no
- Diagnostic functions: no
- Diagnostics information read-out: none
- Supply voltage display: green LED per group
- Group error display: red SF LED
- Channel error display: none
Isolation:
- Between channels: yes
- Between channels of groups up to 8: yes
- Between channels and backplane bus: yes
- Insulation tested with: DC 500 V
Datasizes:
- Input bytes: 1
- Output bytes: 1
- Parameter bytes: 0
- Diagnostic bytes: 0
Housing:
- Material: PPE
- Mounting: Rail System 300
Mechanical Data:
- Dimensions (WxHxD): 40 mm x 125 mm x 120 mm
- Net weight: 240 g
- Weight including accessories: -
- Gross weight: -
Environmental Conditions:
- Operating temperature: 0 °C to 60 °C
- Storage temperature: -25 °C to 70 °C
Certifications:
- UL certification: yes
- KC certification: yes