SM 322 - Digital output
16x DO, in groups of 8
Relay
DC 24 V
AC 230 V
Contact rating per channel 5 A
For 20 pole front connector
SM 322 (322-1HH00)
Technical Data
Order no.: 322-1HH00
Type: SM 322
General Information:
- Note: -
- Features: 16x DO, in groups of 8, Relay, DC 24 V, AC 230 V, Contact rating per channel 5 A, for 20-pin front connector
- SPEED-Bus: no
Current Consumption/Power Loss:
- Current consumption from backplane bus: 80 mA
- Power loss: 4 W
Technical Data Digital Outputs:
- Number of outputs: 16
- Cable length, shielded: 1000 m
- Cable length, unshielded: 600 m
- Rated load voltage: DC 30 V / AC 230 V
- Current consumption from load voltage L+ (without load): -
- Total current per group, horizontal configuration, 40°C: 8 A
- Total current per group, horizontal configuration, 60°C: 8 A
- Total current per group, vertical configuration: 8 A
- Output current at signal "2,5 cm ( 1 inch ), rated value: 5 A
- Signal logic output: isolated
- Output delay of 0 cm ( 0 inch ) to "1: 10 ms
- Output delay of 2,5 cm ( 1 inch ) to "0: 5 ms
- Minimum load current: -
- Lamp load: 6 W
- Parallel switching of outputs for redundant control of a load: not possible
- Parallel switching of outputs for increased power: not possible
- Actuation of digital input: yes
- Switching frequency with resistive load, max.: 0.33 Hz
- Switching frequency with inductive load, max.: 0.33 Hz
- Switching frequency on lamp load, max.: 0.33 Hz
- Internal limitation of inductive shut-off voltage: -
- Short-circuit protection of output: -
- Trigger level: -
- Number of operating cycles of relay outputs: -
- Switching capacity of contacts: 5 A
- Output data size: 2 Byte
Status Information, Alarms, Diagnostics:
- Status display: green LED per channel
- Interrupts: no
- Process alarm: no
- Diagnostic interrupt: no
- Diagnostic functions: no
- Diagnostics information read-out: none
- Supply voltage display: none
- Group error display: none
- Channel error display: none
Isolation:
- Between channels: yes
- Between channels of groups up to 8: yes
- Between channels and backplane bus: yes
- Insulation tested with: AC 1500 V
Datasizes:
- Input bytes: 0
- Output bytes: 2
- Parameter bytes: 0
- Diagnostic bytes: 0
Housing:
- Material: PPE
- Mounting: Rail System 300
Mechanical Data:
- Dimensions (WxHxD): 40 mm x 125 mm x 120 mm
- Net weight: 290 g
- Weight including accessories: -
- Gross weight: -
Environmental Conditions:
- Operating temperature: 0 °C to 60 °C
- Storage temperature: -25 °C to 70 °C
Certifications:
- UL certification: yes
- KC certification: yes