SM 031 - Analog input
2x AI
12 Bit
Current 0(4).20 mA
SM 031 - Analoger Eingang (031-1BB40)
Technical Data:
Order No.:
Type:
Module ID:
General Information:
- Note: -
- Features: 2x AI, 12 Bit, Current 0(4)...20 mA
Current Consumption/Power Loss:
- Current consumption from backplane bus: 80 mA
- Power loss: 0.7 W
Technical Data Analog Inputs:
- Number of inputs: 2
- Cable length, shielded: 200 m
- Rated load voltage: DC 24 V
- Current consumption from load voltage L+ (without load): 15 mA
- Voltage inputs: -
- Min. input resistance (voltage range): -
- Input voltage ranges: -
- Operational limit of voltage ranges: -
- Operational limit of voltage ranges with SFU: -
- Basic error limit voltage ranges: -
- Basic error limit voltage ranges with SFU: -
- Destruction limit voltage: -
- Current inputs: yes
- Max. input resistance (current range): 110 Ohm
- Input current ranges: 0 mA ... +20 mA, +4 mA ... +20 mA
- Operational limit of current ranges: +/-0.3% ... +/-0.5%
- Operational limit of current ranges with SFU: -
- Basic error limit current ranges: +/-0.2% ... +/-0.3%
- Radical error limit current ranges with SFU: -
- Destruction limit current inputs (voltage): max. 24V
- Destruction limit current inputs (electrical current): max. 40mA
- Resistance inputs: -
- Resistance ranges: -
- Operational limit of resistor ranges: -
- Operational limit of resistor ranges with SFU: -
- Basic error limit: -
- Basic error limit with SFU: -
- Destruction limit resistance inputs: -
- Resistance thermometer inputs: -
- Resistance thermometer ranges: -
- Operational limit of resistance thermometer ranges: -
Status Information, Alarms, Diagnostics:
- Status display: yes
- Interrupts: no
- Process alarm: no
- Diagnostic interrupt: no
- Diagnostic functions: yes
- Diagnostics information read-out: possible
- Module state: green LED
- Module error display: red LED
- Channel error display: red LED per channel
Isolation:
- Between channels: -
- Between channels of groups to: -
- Between channels and backplane bus: yes
- Between channels and power supply: yes
- Max. potential difference between inputs and Mintern (Uiso): DC 75 V/AC 50 V
- Insulation tested with: DC 500 V
Datasizes:
- Input bytes: 4
- Output bytes: 0
- Parameter bytes: 6
- Diagnostic bytes: 20
Housing:
- Material: PPE / PPE GF10
- Mounting: Profile rail 35 mm
Mechanical Data:
- Dimensions (WxHxD): 12.9 mm x 109 mm x 76.5 mm
- Net weight: 59 g
- Weight including accessories: 59 g
- Gross weight: 74 g
Environmental Conditions:
- Operating temperature: 0 °C to 60 °C
- Storage temperature: -25 °C to 70 °C
Certifications:
- UL certification: yes
- KC certification: yes