SM 022 - Digital output
2x DO
DC 24 V
0.5 A
PWM up to 40 kHz
Technical Data:
Order No.:
Type:
Module ID:
General Information:
- Note: -
- Features: 2x DO, DC 24 V, 0.5 A, PWM up to 40 kHz
Current Consumption/Power Loss:
- Current consumption from backplane bus: 105 mA
- Power loss: 0.95 W
Technical Data Digital Outputs:
- Number of outputs: 2
- Cable length, shielded: 1000 m
- Cable length, unshielded: 600 m
- Rated load voltage: DC 20.4...28.8 V
- Current consumption from load voltage L+ (without load): 15 mA
- Total current per group, horizontal configuration, 40°C: 1 A
- Total current per group, horizontal configuration, 60°C: 1 A
- Total current per group, vertical configuration: 1 A
- Output current at signal 1, rated value: 0.5 A
- Signal logic output: Sourcing output
- Output delay of 0 to 1: max. 500 ns
- Output delay of 1 to 0: max. 500 ns
- Minimum load current: -
- Lamp load: 10 W
- Parallel switching of outputs for redundant control of a load: not possible
- Parallel switching of outputs for increased power: not possible
- Actuation of digital input: yes
- Switching frequency with resistive load: max. 40 kHz
- Switching frequency with inductive load: max. 40 kHz
- Switching frequency on lamp load: max. 40 kHz
- Internal limitation of inductive shut-off voltage: L+ (-52 V)
- Short-circuit protection of output: yes, electronic, highside only
- Trigger level: 2.5 A
- Number of operating cycles of relay outputs: -
- Switching capacity of contacts: -
- Output data size: 12 Byte
Status Information, Alarms, Diagnostics:
- Status display: green LED per channel
- Interrupts: no
- Process alarm: no
- Diagnostic interrupt: no
- Diagnostic functions: no
- Diagnostics information read-out: possible
- Supply voltage display: green LED
- Group error display: red LED
- Channel error display: none
Isolation:
- Between channels: -
- Between channels of groups to: -
- Between channels and backplane bus: yes
- Insulation tested with: DC 500 V
PWM Data:
- PWM channels: 2
- PWM time basis: 20.83 ns
- Period length: 1200...8388607 * time base
- Minimum pulse width: 1 µs
- Type of output: Push-pull / highside
Safety:
- Safety protocol: -
- Safety requirements: -
- Secure user address: -
- Watchdog: -
- Two channels: -
- Test pulse length: -
- Circuit monitoring: -
Datasizes:
- Input bytes: 4
- Output bytes: 12
- Parameter bytes: 12
- Diagnostic bytes: 20
Housing:
- Material: PPE / PPE GF10
- Mounting: Profile rail 35 mm
Mechanical Data:
- Dimensions (WxHxD): 12.9 mm x 109 mm x 76.5 mm
- Net weight: 61 g
- Weight including accessories: 61 g
- Gross weight: 75 g
Environmental Conditions:
- Operating temperature: 0 °C to 60 °C
- Storage temperature: -25 °C to 70 °C
Certifications:
- UL certification: yes
- KC certification: yes