Further information for Diverse N2XCH 4X50 SM/25 - cable halogen free
Halogen-free cables N2XCH
to VDE 0276-604
Application:
Wherever special protection against fire and fire damage for
Meschen and property is necessary and high security requirements
need to be met. Indoors and outdoors.Not directly
move earth and water. Exposure to flame, they prevent the
expansion of a fire and thereby develop extremely low
smoke. No Absspaltung of toxic and corrosive gases.
They are considered as insulated.
Building:
Conductor: bare copper wire according to VDE 0295,
round solid or stranded
or sector stranded
> 50 mm ² are compressed
Insulation: cross-linked polyethylene 2XI1
Core identification according to VDE 0293
Filling compound
Concentric
Conductor: Bare copper wire
with counter helix of
copper tape, PETP tape
Sheath: polymer mixture
halogen-free according to VDE 0207 T. 24
Color: black
Specifications:
Rated voltage: 06/1 kV
Test voltage: 4000 V
Temperature range: +5 ° C - +50 ° C (during installation)
-30 ° C - +70 ° C (after installation)
Operating temp. +70 ° C (max.)
Bending radius: 12 x cable diameter (stranded)
Tests:
Burning characteristics: according to VDE 0472 T. 804,
Category C (= IEC 332-3)
Corrosivity of gases: according to VDE 0472 T. 813
Smoke density: according to VDE 0472 T. 816,
Category C (= IEC 1034-1)
Halogen-free: according to VDE 0472 T. 815
Ozone resistance: according to VDE 0472 T. 805
Features: Halogen-free
low fire propagation
minimal smoke
no corrosive gases
not directly in the ground and
lay water
cores x nominal cross-section mm ² 4 x 50 RM/25
Cop (kg /% m): 220.3
Outer diameter approx: 34.0
approx Weight (kg / m%): 260.0 Type: N2XCH 4X50/25
Quantity: 1 MTR