Further information for Waskönig+Walter NA2XS2Y 1 X 240,0 RM -
Application:
For laying underground, outdoors (however, the cable must be protected from sunlight), indoors and in cable ducts for power plants, industry and distribution networks. When laying in cable ducts and indoors, it must be taken into account that the PE sheath is not flame-retardant according to VDE 0472 T. 804, test type B. Due to the resistant PE sheath, the cable can be subjected to strong mechanical stress during laying and operation.
Structure:
Conductor: bare aluminum conductor in accordance with
VDE 0295, (RM) round,
multi-wire, extruded
inner conductive layer
Core insulation: VPE (cross-linked polyethylene),
extruded outer conductive layer ,
conductive tape
Shield: copper wires and cross-conducting spiral
made of copper
foil
Outer sheath: black PE
Technical data:
Nominal voltage: 6/10 kV, 12/20 kV and 18/30 kV
Test voltage: 21 kV AC/5 min. at Uo/U=6/10 kV
30 kVAC/5 min. at Uo/U=12/20
kV 45 kV AC/5 min. at Uo/U=18/30 kV
Temperature range: -20 °C - +70 °C (during installation)
-30 °C - +70 °C (after installation)
Operating temperature: +90 °C (max.)
Bending radius: 15 x cable diameter.