| General |
| Nominal voltage | 450/750 V |
| Test voltage | 2500 V |
| Installation temperature range | +5 °C - +70 °C |
| Temperature range after installation | -30 °C - +70 °C |
| Operation temperature | +70 °C |
| Bending radius | 15 x cable diameter |
| Flame retardancy | VDE 0472 T. 804 test type B (=IEC 332-1) |
| Conductor | Copper bare, solid |
| Insulation | PVC according to VDE 0207 |
| Sheath colour | Brown |
| Colour standard | VDE 0293-308 |
The H07V-U 4 BR wiring cable from VDE-Kabel is a PVC-insulated single-core cable for use in electrical installations indoors. It is intended for installation in conduits, on, in, and under plaster, as well as in closed installation channels. The cable is also designed for internal wiring of devices, control panels, and distributors, and can be used in protected installations within and on luminaires. Use on trays, channels, or troughs is explicitly not permitted.
Applications
This cable is designed for dry rooms and is suitable for use in switching and distribution systems. It is suitable for applications where the rated voltage does not exceed 450/750 V. The maximum operating temperature is 70 °C, and the cable must be installed at a temperature of at least +5 °C. After installation, it can be operated at -30 °C, provided the operating temperature does not exceed 70 °C.
Functions and Features in Detail
The cable consists of a bare, single-strand copper conductor, insulated with PVC according to VDE 0207. The sheath colour complies with standard VDE 0293-308 and is brown in this case. The colour serves for identification and is relevant for integration into electrical installations. The cable is rated for a nominal voltage of 450/750 V, making it suitable for a wide range of standard applications in electrical installation construction.
Technical Explanation
The test voltage is 2500 V, confirming the electrical strength of the insulation under test conditions. Flame retardancy complies with VDE 0472 Part 804, Test Method B, equivalent to IEC 332-1. This means that during a fire test under defined conditions, the cable does not produce flames or flame propagation, which is important for safety in buildings. The minimum bending radius is 15 times the cable diameter, which must be considered during installation to ensure mechanical integrity.
Compatibility and Accessories
The cable is designed for use in standard installation systems and can be connected to common installation components such as cable lugs, plug connectors, and switches. Installation in closed channels or conduits is intended, while direct installation on open supports such as trays or channels is not permitted. The cable is not intended for outdoor use or in damp environments, as no specific protection rating such as IP67 or similar is specified.
Installation and Mounting
Installation takes place in closed installation systems, with the cable being routed in conduits or channels. Installation must occur at a temperature of at least +5 °C to ensure proper processing of the PVC insulation. After installation, the cable can be operated at temperatures down to -30 °C, although the operating temperature must not exceed 70 °C. The minimum bending radius of 15 times the cable diameter must be observed to avoid cracks or mechanical damage to the insulation.
Operational Advantages
The cable offers high electrical strength and is flame retardant, enhancing safety in electrical installations. The PVC insulation ensures good mechanical stability and chemical resistance against typical indoor environmental conditions. The brown sheath colour facilitates identification and integration into electrical circuit diagrams. The cable is suitable for a wide range of standard applications in electrical installation construction and complies with common standards for wiring cables.