Further information for Diverse NHXH-E90 12 X 1,5 - NHXH E90 12x1 5 ² orange halogen free sheath line
Halogen-free cables with insulation and integrity NHXH FE 180 E90
Application:
Safety cables are eingsetzt wherever special protection against fire and fire damage to people and property is necessary and high Notlaufzeiten must be met, such as. Airports, hospitals and schools Indoor and outdoor use, but do not lay directly in the ground and water. The fire caused by smoke emission, which makes the escape routes found and the development of toxic gases causes is prevented. Insulation from at least 180 minutes integrity and security of at least 90 minutes more than 90 minutes guaranteed the functionality when water pressure boosting systems for fire water supply, ventilation systems, smoke and heat exhaust ventilation systems and fire lifts, etc.
Building:
Conductor: bare copper wire according to VDE 0295, round solid or stranded wire > 50 mm2 are compressed mica tape insulation: polymer mixture halogen-free according to VDE 0207 T. 23
Colour code:
drawing: according to VDE 0293
Common
Inner covering: glass silk ribbons or extruded filling compound, foil wrapping Sheath: polymer mixture halogen-free according to VDE 0207 T. 24 Jacket Color: Orange
Specifications:
Rated voltage: 06/1 kV
Test voltage: 4000 V
Temperature range: +5 ° C - +50 ° C (during installation)
-30 ° C - +70 ° C (after installation)
Operating temp. +90 ° C (max.) Bending radius: 10 x cable diameter (fixed)
Tests:
Burning characteristics: according to VDE 0472 T. 804, Category C (= IEC 332-3) Insulation: VDE 0472 T. 814 and IEC 331 Function maintenance: according to VDE 0472 T. 804 and IEC 332-3 corrosivity of fire gases: according to VDE 0472 T . 813 Smoke density: according to VDE 0472 T. 816, Category C (= IEC 1034-1) Type: NHXH-E90 12 X 1.5 Quantity: 1 MTR