| General |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Installation temperature range | +5 °C |
| Temperature range after installation | -30 °C |
| Bend radius single-core | 15 x cable diameter |
| Bending radius multi-core | 12 x cable diameter |
| Flame retardancy | EN 50266-2-4, IEC 60332-3 Cat.C |
| Insulation integrity | FE 180 according to VDE 0472 Part 814 |
| Circuit integrity | E 90 according to DIN 4102-12 |
| Wire insulation | networked halogen-free ceramisable insulation HXI2 |
| Conductor marking | according to VDE 0293-308 |
| Outer sheath | halogen-free polymer blend orange |
| Conductor | Copper conductor, bare, solid or stranded |
| Features | halogen-free, flame-retardant, minimal smoke emission, no corrosive gases |
The NHXH 5X16 E90 cable from VDE-Kabel is a halogen-free power cable specifically developed for applications with high fire protection requirements. It ensures safe power supply in buildings where maintaining functionality during a fire is critical, for example in fire alarm systems, emergency lighting, or alarm systems in accordance with VDE 108. The cable is intended for indoor use and can be installed in air, concrete, or conduit, provided no water accumulation occurs in the conduit. Direct installation in soil or water is not permitted. The cable is suitable for connecting devices of protection class II and requires protection against external influences and mechanical damage during installation.
Applications
This cable is used in areas requiring high fire and fire damage safety, particularly in public buildings, hospitals, administrative buildings, or industrial facilities. It is designed for use in systems that must remain operational during a fire, such as fire alarm systems, emergency lighting, and systems for alerting and instructing people. The approval according to DIN 4102-12 (E30) ensures that the cable maintains its electrical function even after 90 minutes of fire exposure (E90). Testing was performed for all standard cable support systems, including cable trays, ladders, and ceiling installations.
Functions and Equipment in Detail
The cable consists of bare copper conductors, either single-strand or multi-strand. The conductor insulation is made of a cross-linked, halogen-free, ceramifiable storage insulation (HXI2), which forms a stable, ceramic layer at high temperatures, thus maintaining electrical insulation even during a fire. Conductor identification follows VDE 0293-308. A common sheath protects the individual conductors, and the outer jacket is made of a halogen-free polymer mixture in orange, providing visual identification and differentiation.
Technology Explained Simply
The ceramification of the insulation at high temperatures ensures that electrical insulation is maintained even during a fire. The functional integrity test (E90) according to DIN 4102-12 means the cable withstands 90 minutes of fire exposure without losing its electrical conductivity. The insulation integrity test (FE 180) according to VDE 0472 T. 814 confirms that the insulation retains its electrical properties even after 180 minutes of fire exposure. Flame retardancy according to EN 50266-2-4 and IEC 60332-3 Cat.C indicates that the cable is difficult to ignite and does not propagate flames. The halogen-free composition prevents the release of toxic, corrosive gases and minimizes smoke development during a fire.
Compatibility and Accessories
The cable is designed for use in electrical installations with a rated voltage of 300/500 V and can be installed in standard support systems such as cable trays, ladders, or ceiling installations. It is suitable for connecting devices of protection class II. Conduit installation is permitted, provided no water accumulation occurs. The cable installation must be designed such that the conductor resistance at 800 °C (final temperature during E30 test) is approximately four times higher than at 20 °C, which must be considered during sizing.
Installation and Mounting
During installation, a minimum temperature of +5 °C must be observed. After installation, the cable can be operated at temperatures from -30 °C to +70 °C. The bending radius is 15 times the cable diameter for single-conductor cables and 12 times for multi-conductor cables. Cables must be protected against mechanical damage and external influences. Installation is carried out indoors, in air, concrete, or conduit, with conduit installation only permitted if no water accumulation occurs.
Operational Advantages
The cable offers high fire safety through functional integrity (E90) and insulation integrity (FE 180). The halogen-free composition minimizes smoke development and prevents the release of corrosive gases, facilitating rescue and evacuation. The ceramifiable insulation ensures stable electrical performance even at high temperatures. The orange color of the outer jacket facilitates visual identification within the installation network. The approval for use in safety systems according to VDE 108 makes this cable a reliable choice for critical applications.