Halogen-free cables with insulation and
Integrity NHXH FE 180 E90
Application:

Safety cables are eingsetzt wherever special protection against fire and fire damage to people and property is necessary and high Notlaufzeiten must be met, such as. Airports, hospitals and schools Indoor and outdoor use, but do not lay directly in the ground and water. The fire caused by smoke emission, which makes the escape routes found and the development of toxic gases causes is prevented. Insulation from at least 180 minutes integrity and security of at least 90 minutes more than 90 minutes guaranteed the functionality when water pressure boosting systems for fire water supply, ventilation systems, smoke and heat exhaust ventilation systems and fire lifts, etc.

Building:


Conductor: bare copper wire according to VDE 0295,
round solid or stranded

50 mm2 are compacted

Mica tape
Insulation: polymer blend
Halogen-free according to VDE 0207 T. 23
Colour code:
drawing: according to VDE 0293
Common
Inner covering: glass silk ribbons or
extruded filling compound,
Foil wrapping
Sheath: polymer blend
Halogen-free according to VDE 0207 T. 24
Jacket color: Orange

Specifications:


Rated voltage: 06/1 kV
Test voltage: 4000 V
Temperature range: +5 ° C - +50 ° C (during installation)
-30 ° C - +70 ° C (after installation)
Operating temp. +90 ° C (max.)
Bending radius: 10 x cable diameter
(Fixed)

Tests:

Burning characteristics: according to VDE 0472 T. 804,
Category C (= IEC 332-3)
Insulation: VDE 0472 T. 814
and IEC 331
Function maintenance: according to VDE 0472 T. 804
and IEC 332-3
Corrosivity
Gases: according to VDE 0472 T. 813
Smoke density: according to VDE 0472 T. 816,
Category C (= IEC 1034-1)
Type: NHXH 3X2, 5 E90
Quantity: 1 MTR
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

http://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/578337
qrcode für Diverse NHXH 3X2,5 E90 - NHXH E90 3x2 5 sqmm orange halogen free sheath line