| General |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Installation temperature range | +5 °C - +70 °C |
| Temperature range after installation | -30 °C - +70 °C |
| Bend radius single-core | 15 x cable diameter |
| Bending radius multi-core | 12 x cable diameter |
| Flame retardancy | according to EN 50266-2-4, IEC 60332-3 Cat.C |
| Insulation integrity | FE 180 according to VDE 0472 T. 814 |
| Circuit integrity | E 30 according to DIN 4102-12 |
| Conductor marking | according to VDE 0293-308 |
| Sheath colour | Orange |
| Conductor material | Copper, bare, solid or stranded |
| Insulation material | Networked, halogen-free, ceramizing 2-layer insulation HXI2 |
| Protection class | II |
| Features | halogen-free, flame-retardant, minimal smoke emission, no corrosive gases |
The NHXH 5X1.5 E30 cable from VDE-Kabel is a halogen-free power cable specifically developed for applications with high fire protection requirements. It is designed for safe power supply in buildings where the protection of people and property in the event of fire is of critical importance. The cable is intended for indoor use, particularly for air or concrete installation, and can also be installed in conduits, provided no water accumulation occurs. Direct installation in soil or water is not permitted. It is suitable for connecting devices of protection class II and meets the requirements for functional integrity according to DIN 4102-12 (E30), qualifying it for use in fire alarm systems, alarm and instruction systems, as well as safety and emergency lighting in accordance with VDE 108. The design of cable systems with functional integrity requires consideration that the conductor resistance at 800 °C (final temperature of the E30 test) is approximately four times higher than at 20 °C.
Applications
This cable is used in areas where high fire resistance and the maintenance of electrical function during a fire are required. This includes buildings with high visitor traffic, such as hospitals, schools, administrative buildings, or public transport facilities. It is suitable for installation in cable trays, cable ladders, and ceiling installations. The application is limited to indoor environments, where the cable must be protected against external mechanical influences. Its use in fire alarm systems and safety lighting systems is permitted due to the passed E30 test.
Functions and Features in Detail
The cable features a cross-linked, halogen-free, ceramizing two-layer insulation (HXI2), providing high thermal stability and fire resistance. Conductor identification follows VDE 0293-308, enabling clear identification of individual conductors. The common conductor sheathing and the orange outer jacket made from halogen-free polymer mixture ensure clear visual distinction and enhanced visibility. The conductors are made of bare copper, available in both single- and multi-strand configurations. The orange outer jacket serves as a visual identifier and is commonly used in electrical installations for special applications.
Technical Explanation
The ceramization of the insulation means that the insulation transforms into a ceramic material at high temperatures, maintaining electrical insulation even during a fire. This is crucial for functional integrity. Testing according to DIN 4102-12 (E30) guarantees that the cable maintains its electrical function for 30 minutes at an ambient temperature of 800 °C. Flame retardancy according to EN 50266-2-4 and IEC 60332-3 Cat.C, as well as insulation integrity FE 180 according to VDE 0472 T. 814, provide additional safety features. The rated voltage is 300/500 V, with a test voltage of 2000 V. Installation temperature range is +5 °C to +70 °C, and operating temperature range after installation is -30 °C to +70 °C. The minimum bending radius is 15 times the cable diameter for single-core and 12 times for multi-core conductors.
Compatibility and Accessories
The cable is designed for use in standard cable support systems such as cable trays, cable ladders, and ceiling installations. It is suitable for connecting devices of protection class II. Installation in conduits is permitted, provided no water accumulation occurs. It is not intended for direct installation in soil or water. Its use in fire alarm systems, alarm and instruction systems, as well as safety and emergency lighting is permitted due to the passed E30 test.
Installation and Mounting
During installation, care must be taken to protect the cable from mechanical damage and external influences. Installation is carried out indoors, in air or concrete. Conduit installation is allowed if water accumulation is excluded. Bending radii depend on conductor structure: 15 times the diameter for single-core and 12 times for multi-core conductors. Installation temperature limits range from +5 °C to +70 °C, and operating temperature limits after installation range from -30 °C to +70 °C.
Operational Advantages
The cable provides high safety in the event of fire through halogen-free, ceramizing insulation, ensuring minimal smoke development and no formation of corrosive gases. The 30-minute functional integrity at 800 °C ensures that critical systems such as fire alarm systems or safety lighting continue to operate during a fire. The halogen-free composition reduces fire hazard and protects people and materials from toxic by-products. Clear conductor identification and the orange outer jacket facilitate installation and maintenance.