Further information for Diverse NHXCH 4X50/25 E30 - NHXCH E30 4x50 0/25 0qmm halogen free sheath line
Halogen-free cables NHXCH FE 180 E 30
with insulation and integrity, shielded
Application:
Wherever special protection against fire and fire damage to
people and property is necessary and high Notlaufzeiten met
must be such Beisspiel in airports, hospitals and
schools. Indoor and outdoor use, not directly in the ground
water and embarrassed. The development resulting from fire toxic
gases causing shear is prevented. Insulation of at least
180 minutes integrity of at least 30 minutes. Security
over 30 minutes, for example, guarantees the operability of
fire detection and alarm systems, security and other
emergency power lighting.
Building:
Conductor: bare copper wire according to VDE 0295,
round solid or stranded
> 50 mm ² are compacted
Mica tape
Insulation: polymer mixture halogen-free
according to VDE 0207 T. 23
Core identification to VDE 0293 (dischargers always in
O version) core covering
Inner covering: glass silk ribbons or
extruded filling compound
Concentric conductor: Bare copper wire with opposite-
läufiger helix of copper tape,
PETP tape
Sheath: polymer mixture halogen-free
according to VDE 0207 T. 24
Jacket color: Orange
Specifications:
Rated voltage: 06/1 kV
Test voltage: 4000 V
Temperature range: +5 ° C - +50 ° C (during installation)
-30 ° C - +70 ° C (after installation)
Operating temp. +90 ° C (max.)
Bending radius: 10 x cable diameter
(Fixed)
Tests:
Burning characteristics: according to VDE 0472 T. 804,
Category C (= IEC 332-3)
Insulation: VDE 0472 T. 814 and IEC 331
Function maintenance: according to VDE 0472 T. 804 and IEC 332-3
corrosivity of fire gases: according to VDE 0472 T. 813
flue gas you
type: E30 NHXCH 4X50/25
Quantity: 1 MTR