Further information for Diverse NYCWY 3X150 SM/70 - NYCWY 3x150 sq SM / 70 qmmTrommel PVC insulated earth cable conc Head
			
			Underground NYCWY
  according to VDE 0276
  Application:
  As power and control cable for use primarily for industrial
  and substations and power plants,
  where increased mechanical
  Electric shock protection is required.
  Building:
  Conductor: bare copper wire according to VDE 0295,
  (RE) solid round
  Insulation: PVC
  Colour code:
  drawing: according to VDE 0293
  Filling compound
  Concentric
  Conductor: Bare copper wire to the
  inner covering ver-roping
  with counter helix of copper tape
  (Copper wires in the inner liner,
  Copper strip in the outer layer)
  Sheath: PVC black
  Specifications:
  Rated voltage: 0.6 / 1 kV
  Test voltage: 4 kV
  Temperature
  range: - 5 ° C - + 50 ° C (during installation)
  - 30 ° C - + 70 ° C (after installation)
  Operating
  temperature: + 70 ° C (max.)
  Bending radius: 12 x cable diameter
  Flame resistance according to VDE 0472 T.
  804 class B (= IEC 332-1)
  Number of cores x cross-section mm ²: 3 x 150SM/70
  Outer diameter approx: 46
  Copper content (kg / m%): 510.0
  Weight (kg / m%): 600.0
  Type: NYCWY 3x150 SM/70
  Quantity: 1 MTR