Further information for H07RN-F H07RN-F 5G10 TR - 5G10 ² Heavy rubber cable
			
			Heavy rubber cable H07RN-F
  according to VDE 0282-4
  Application:
  For connection of equipment under very extreme
  Loads, both mechanical and thermal point of view.
  For example, for equipment used in agricultural, industrial and fire-hazard
  ten operating sites.  Next they are for large boilers, heating plates,
  Hand lamps, electric tools such as circular saws, drills,
  Home network devices, but also for transportable motors or machines
  used on construction sites or farms, etc.,
  can also be used for fixed installation, eg on plaster, in temporary
  Buildings and barracks, allowed for direct laying aud components
  of lifting equipment, machinery, etc.
  Building:
  Conductor: Stranded bare copper Class 5
  Insulation: rubber compound according to VDE 0207 T. 20
  Core identification according to VDE 0293
  Outer sheath: rubber compound according to VDE 0207 T. 21
  Color: black
  Specifications:
  Rated voltage: 450/750 V
  Test voltage: 2500 V
  Temperature range: - 25 ° C - + 60 ° C (during installation)
  - 40 ° C - +60 ° C (after installation)
  Operating temp. +60 ° C (max.)
  Bending radius: 6 x cable diameter (min.)
  Dauerzugbelastung: max.  15N/mm 2 taking into account the
  Total copper cross section
  Fire: according to VDE 0472 T. 804
  Category B (= IEC 332-1)
  Oil resistance of sheath: VDE 0472 T. 803 Category A
  Ozone resistance: according to VDE 0472 T. 805 Category A or
  according to VDE 0472 T. 805 A1 Category C
  Number of cores x cross-section mm ²: 5 G 10
  Copper content (kg / m%): 48.0
  Outer diameter approx: 29.1
  Weight (kg / m%): 100.1
  Type: H07RN-F 5G10 TR
  Quantity: 1 MTR