Further information for Waskönig+Walter NYCWY 4X35 SM/16 - NYCWY 4x35 sq SM / 16 sq drum PVC insulated earth cable conc Head
Underground NYCWY
according to VDE 0276
Application:
As power and control cable for use primarily for industrial
and substations and power plants,
where increased mechanical
Electric shock protection is required.
Building:
Conductor: bare copper wire according to VDE 0295,
(RE) solid round
Insulation: PVC
Colour code:
drawing: according to VDE 0293
Filling compound
Concentric
Conductor: Bare copper wire to the
inner covering ver-roping
with counter helix of copper tape
(Copper wires in the inner liner,
Copper strip in the outer layer)
Sheath: PVC black
Specifications:
Rated voltage: 0.6 / 1 kV
Test voltage: 4 kV
Temperature
range: - 5 ° C - + 50 ° C (during installation)
- 30 ° C - + 70 ° C (after installation)
Operating
temperature: + 70 ° C (max.)
Bending radius: 12 x cable diameter
Flame resistance according to VDE 0472 T.
804 class B (= IEC 332-1)
Number of cores x cross-section mm ² 4 x 35SM/16
Outer diameter approx: 30
Copper content (kg / m%): 152.6
Weight (kg / m%): 210.0
Type: NYCWY 4X35 SM/16
Quantity: 1 MTR