Further information for Waskönig+Walter NAYY-J 4X120 - NAYY 4x120 ² SE aluminum underground cable drum
Power cables NAYY J-aluminum conductors
according to VDE 0276
Application:
As power and control cable for use in open air, in the ground, for power stations, industry and switchgear, in water, in dry and humid indoors, in cable ducts as well as in subscriber networks, where mechanical damages are not to be expected.
Building:
Conductor: Aluminum conductor according to VDE 0295,
(RE) solid round or
(SE) sector shaped solid or
(SM) sector stranded
Insulation: PVC
Colour code:
drawing: according to VDE 0293
Filling compound
Sheath: PVC black
Specifications:
Rated voltage: 0.6 / 1 kV
Test voltage: 4 kV
Temperature
range: - 5 ° C - + 50 ° C (during installation)
- 30 ° C - + 70 ° C (after installation)
Operating
temperature: + 70 ° C (max.)
Bending radius: 12 x cable diameter
Flame resistance according to VDE 0472 T.
804 class B (= IEC 332-1)
Number of cores x cross-section mm ² 4 x 120SE
Outer diameter approx: 44
AL-figure kg / km 139.2
Weight (kg / m%): 280.0
Type: NAYY J 4x120 item: 1 MTR