Further information for Waskönig+Walter NYCWY 4X50 SM/25 - NYCWY 4x50 sq SM / 25 sq drum PVC insulated earth cable conc Head
Underground NYCWY
according to VDE 0276
Application:
As power and control cable for use Primarily for industrial
and power plants and substations,
where Increased mechanical
protection is required against contact voltage.
Building:
Conductor: bare copper wire according to VDE 0295,
(RE) solid round
Insulation: PVC
Colour code:
drawing: according to VDE 0293
Filling compound
Concentric
Conductor: Bare copper wire around the
inside covering ver-roping
with counter Helix of copper tape
(copper wires in the inner liner,
copper strip in the outer layer)
Sheath: PVC black
Specifications:
Rated voltage: 0.6 / 1 kV
Test voltage: 4 kV
Temperature
range: - 5 ° C - + 50 ° C (during installation)
- 30 ° C - + 70 ° C (after installation)
Operating
temperature: + 70 ° C (max.)
Bending radius: 12 x cable diameter
Flame resistance according to VDE 0472 T.
804 class B (= IEC 332-1)
Number of cores x cross-section mm ² 4 x 50SM/25
Outer diameter approx: 34
Cop (kg / m%): 220.3
Weight (kg / m%): 285.0 Type: NYCWY 4X50 SM/25
Quantity: 1 MTR