Further information for Waskönig+Walter NYCY 3 X 2,5 RE/2,5 - NYCY RE2 5 3x2 5 sq PE insulated earth cable conc Head
Application:
As a permanently installed power and control cable for use primarily in industrial and switchgear installations and in power plants where increased mechanical protection against contact voltage is required.
Structure:
Conductor: bare copper conductor in accordance with VDE 0295,
(RE) round, single-wire
Core insulation: PVC
Core identification: in accordance with VDE 0293-308 1 to 5 cores,
from 7 cores black with white numbers
Filling jacket
Concentric conductor: made of bare copper wires stranded around the
common core sheath
with a counter helix made of
copper tape (copper wires in the
inner layer, copper tape in the
outer layer)
Outer jacket: black PVC
Technical data:
Nominal voltage: 0.6 /1 kV
Test voltage: 4 kV
Temperature range: -5 °C - +50 °C (during installation)
-30 °C - +70 °C (after installation)
Operating temperature: +70 °C (max.)
Bending radius: 12 x cable diameter
Flame retardancy: in accordance with VDE 0472 T.
804 test type B (=IEC 332-1).