Further information for Waskönig+Walter NYCY 3X1,5 RE/1,5 - NYCY 3x1 5 sqmm RE / 1 5 sqmm PVC insulated earth cable conc
Underground NYCY
according to VDE 0276
Application:
As power and control cable for use primarily for industrial and power plants and substations,
where increased mechanical protection is required against contact voltage.
Building:
Conductor: bare copper wire according to VDE 0295,
(RE) solid round
Insulation: PVC
Colour code:
drawing: according to VDE 0293
Filling compound
Concentric
Conductor: Bare copper wire to the
inner covering ver-roping
with counter helix of copper tape
(Copper wires in the inner liner,
Copper strip in the outer layer)
Sheath: PVC black
Specifications:
Rated voltage: 0.6 / 1 kV
Test voltage: 4 kV
Temperature
range: - 5 ° C - + 50 ° C (during installation)
- 30 ° C - + 70 ° C (after installation)
Operating
temperature: + 70 ° C (max.)
Bending radius: 12 x cable diameter
Flame resistance according to VDE 0472 T.
804 class B (= IEC 332-1)
Number of cores x cross-section mm ²: 3 x 1.5 RE / 1.5
Outer diameter approx: 14
Copper content (kg / m%): 6.6
Weight (kg / m%): 25.0
Type: NYCY 3X1, 5 RE / 1.5
Quantity: 1 MTR