'Erdkabel NYY-J / NYY-O
according to VDE 0276
Application:
As power and control cables for use outdoors, in the ground,
indoors and in cable ducts.
Construction:
Conductor: bare copper, according to VDE 0295,
(RE) round solid or
(RM) Circular stranded
(
50 are qmm compressed) or
(SE) sector-shaped solid or
(SM) sector-shaped stranded
Core insulation: PVC
Colour code:
drawing: according to VDE 0293
J = with green-yellow. Protective conductor
O = without gr./ge. Protective conductor
filling compound
Outer sheath: PVC black
Technical specifications:
Rated voltage: 0.6 / 1 kV
Test voltage: 4 kV
Temperature-
range: - 5 ° C - + 50 ° C (during installation)
- 30 ° C - + 70 ° C (after laying)
Operating
temperature: + 70 ° C (max.)
bending radius: 15 x cable diameter
(single core)
12 x cable diameter
(stranded)
flame resistance according to VDE 0472 T.
804 test B (= IEC 332-1)
underground cable NYY-J
number of cores x nominal cross section mm²: 3 x 6 RE
outer diameter approx .: 15
copper weight (kg /% m): 17 3
weight (kg / m%): 48.0
'item: 1 MTR