Shielded sheathed cables (N)YM-(St)-J Application:
These shielded installation cables effectively limit electromagnetic interference fields using a static shield. This shielding is particularly used for installation in computer areas, in hospitals or in industrial control rooms with particularly sensitive measuring devices.
This cable is also suitable for installation in the living area of radiation-sensitive and particularly sensitive people. Use in hazardous areas is not permitted. For installation in dry and wet rooms on, in and under plaster, in masonry and in concrete (except for shaken, vibrated or rammed concrete). When used outdoors, the cable must be protected from direct sunlight.
Structure:
Conductor: bare copper conductor
- 10 mm² single-wire
> 10 mm² multi-wire
Core insulation: PVC in accordance with VDE 0207 T. 4
Marking: in accordance with VDE 0293-308
Shield: plastic-coated aluminum foil with
drain wire 1.5 mm²
filling jacket
Outer jacket: PVC gray
Technical data:
Nominal voltage: 300/500 V
Test voltage: 2000 V
Temperature
range: +5 °C - +70 °C (when laying)
-40 °C - +70 °C (after laying)
Operating temperature: +70°C (max.)
Bending radius: 4 x cable diameter
(fixed laying).
(N)YM-(St)-J