Further information for Xaver Bechtold H07V-R 70,0 SW - H07V 70 ² black PVC insulated single conductor
PVC wire, H07V-R
Accor ding to VDE 0281-3
Application:
In dry rooms, switch and distribution system as well as
in pipes, on and under plaster as well as in closed installation
ducts. The Following Following uses are for laying
Provided this PVC core: The internal wiring of
appliances, switchgear and distribution and the AC or
a DC voltage up to 750 V to ground. It is not suitable for
the direct Verlegungauf racks, troughs or tubs.
Building:
Conductor: Bare copper, stranded
Insulation: PVC Accor ding to VDE 0207
Sheath color: according to VDE 0293
Specifications:
Rated voltage: 450/750 V
Test voltage: 2500 V
Temperature range: +5 ° C - +70 ° C (during installation)
-30 ° C - +70 ° C (after installation)
Operating Temp +70 ° C (max )
Bend radius: 15 x cable diameter (min.)
Flame resistance Accor ding to VDE 0472 T. 804
test method B (= IEC 332-1)
70.0 sqmm, OD: 14.5 mm, Copper weight: 67.2 kg / m%
Color: black
Copper content (kg / m%): 67.2
Outer diameter approx: 14.5
Weight (Kg / m%): 75.0 Type: H07V-R 70.0 SW item: 1 MTR