Further information for VDE-Kabel H05RN-F 3G1,0 (1609006)
Application
This cable is used for connecting electrical devices subject to medium mechanical stress in dry, damp and wet rooms as well as outdoors as a connection cable for garden equipment such as lawn mowers, etc. They may come into contact with grease and oil.
Construction
Conductor: Fine-wire copper wire class 5
bare or tinned
Core insulation: Rubber compound in accordance with
VDE 0207 T. 20
Core identification: in accordance with VDE 0293-308
Outer sheath: Rubber compound in accordance with
VDE 0207 T. 21
Sheath colour: black
Note
G = with green-yellow protective conductor
X = without protective conductor
Technical data
Nominal voltage: 300/500 V
Test voltage: 2000 V
Temperature range: -25 °C - +60 °C (during installation)
-40 °C - +60 °C (after installation)
Operating temperature: +60 °C (max.)
Bending radius: 7.5 x cable diameter (min.)
Fire behaviour: in accordance with VDE 0472 T. 804
test type B (=IEC 332-1)
Oil resistance of the
sheath: in accordance with VDE 0472 T. 803 test type A
Ozone resistance: in accordance with VDE 0472 T. 805 test type A or
according to VDE 0472 T. 805 A1 test type C.