Further information for Diverse JE-LIYCY-BD 20X2X0,5 - JE LIYCY 20x2x0 5 electronic cable copper shielding
Application
The cables are used to transmit signals and measured values in symmetrical circuits in control and regulation technology, as well as to transmit information in data and process computer systems. Suitable for flexible use and fixed installation in dry and damp rooms in and under plaster, but also for fixed installation on external walls of buildings. With blue outer sheath for intrinsically safe systems. Installation cables are not approved for high-voltage installation purposes or for underground installation.
Construction
Conductor: bare copper wire 7 x 3.0 mm
Core insulation: PVC, 0.3 mm wall thickness
Core identification: according to Siemens color code
Stranding: 4 pairs in a bundle
Bundle in layers
of foil
Shielding: tinned copper braid
Sheath: PVC gray or blue
Technical data
Conductor resistance of the loop: max. 78.4 Ohm/km
Insulation resistance: min 100 MOhmxkm
Capacitive coupling: max. 200 pF/100 m
Operating capacitance at 800 Hz: max. 100 nF/km
Test voltage:
Core/core 500 V 50 Hz ^1 min.
Core/shield 2000 V 50 Hz ^1 min.
Peak operating voltage: 225 V
Temperature range:
moving: -5 °C to + 50 °C
stationary: -30 °C to +70 °C
Bending radius: 7.5 x cable diameter.