Further information for Lappkabel OEZCUY-O(E) 12X0,75 - Lapp olflex EB CY 12x0 75 ² shielded control cable intrinsically
Control line YSLCY-O (E) shielded,
intrinsically safe, blue
Application:
Supply and connecting cables for intrinsically safe circuits. Suitable for fixed installation or flexible application, with free movement without tensile stress or forced movements. The control cable can be used in dry, damp and wet areas with medium mechanical stresses. Moreover, it can be used to control equipment in hazardous areas. When used as a signal or measurement line frequency external influences are parried by the copper shield.
Building:
Conductor: Bare copper, fine wire
Insulation: PVC
Colour code:
drawing: O = black cores with consecutive numbers without protective conductor
twisted in layers
Shielding: tinned copper braid
Jacket: PVC
Color: blue
Specifications:
Rated voltage: 300/500 V
Test voltage: 3000 V
Temperature range: + 5 ° C to + 70 ° C (dynamic)
-30 ° C to +70 ° C (non-moving)
Bending radius: 7,5 x cable diameter
Flame resistance according to VDE 0472 T. 804 class B (IEC 332-1 =)
Number of cores x cross section sqmm: 12 x 0.75
Outer diameter approx: 11.0
Copper content (kg / m%): 13.80
Approximate weight (kg / m%): 232.0
Type: ÖZCuY-O (E) 12X0, 75
Item: 100 MTR