The cabinet height is specified without the levelling feet supplied in the accessories pack. If these feet are mounted, the installation dimension of the cabinet is increased by 24 to 35 mm.
Height unit
18U
Door height
768mm
Front door
Glass door left hinge
Depth
1000mm
Recommended maximum load
1200/1500kg
Packaging volume
0.5400m³
Maximum spacing of vertical rails
884mm
Protection class
IP20
Rear panel/door
Solid sheet metal rear panel, with two safety locks
Width packaging
0.600m
Height (outside)
900mm
Length packaging
1.000m
Height packaging
0.900m
Width
600mm
Detachable rear panel
Detachable side panels
Demountable
Bolted, easy to dismantle stand distributor, IP20, load capacity 1200/1500 kg
FRAME MOUNTING
with fittings and screws. Sheet steel 1.3 mm.
TRITON SWIVELLING LEVER HANDLES
By replacing the plastic module (not included), it is possible to choose between a classic and semi-cylindrical closure. Patent: PUV 2013-27443.
WIDER CABINET CORNERS
allow the mounting of accessories, cable management panels and socket strips.
ENCLOSURE TAPE
1m in accessory pack
PERFORATED SUPPORTS
The openings along the entire height of the uprights correspond to the HE spacing of the verticals.
LASER DESIGNATION OF THE VERTICALS
Sheet steel 2mm
FLEX FRAME
The four-point support allows the installation of adjustable slats at 48,3 cm ( 19 inch ), 53,3 cm ( 21 inch ) and 58,4 cm ( 23 inch ) spacing for 800 mm wide distribution boards. Sheet steel 2.5mm.
EARTHING
All removable parts are interconnected in accordance with the requirements of the relevant standards.
BREAK-OUT PANELS
The large opening provided with a break-out facing allows a Triton fan panel to be fitted and removed from the outside without the need for screws. The cable entries in the rear part of the distributor are provided with break-out blind plates. They can be sealed against dust with the brush strip. A plastic frame is used to protect the cables from damage (both are included in the accessory pack).
M8 MAIN EARTHING POINT
CABLE INSTALLATION
Installation of the accessories without having to pull the cables through.
OPTIONAL STRENGTH INCREASE from 1,200kg to 1,500kg
The closed 1.5mm (4-piece) thick profile increases the load-bearing capacity of the 800mm wide manifold to 1,500kg. (RAX-VR-Txx-X2)
DESCRIPTION, INTENDED USE 48,3 cm ( 19 inch ) floor-standing distribution board with IP20 protection rating
The distribution board includes 4 adjustable vertical rails for mounting the components (6 in distribution boards deeper than 800 mm).
Distribution board construction: welded steel construction with removable walls / single or double doors in the versions solid sheet, perforated (80% air passage) or glass door with 4 mm thick safety glass. They can be mounted at the front or rear of the distribution board / Preparation for mounting vertical cable routing panels and socket strips, including fixings, on the frame / Preparation for easy baying of cabinets.
The permissible load capacity of the individual doors is 20 kg max.
The minimum application thickness is 65 microns
These cabinets are designed for the installation of data and telecommunication equipment and their distribution systems
The distribution frame as well as all removable parts (side and rear panels, doors, ?) are connected with earthing cables, which must be properly fixed and plugged in during the entire service life of the cabinet
There is an M8 screw in the bottom of the distribution board as the main earthing point
Cable entries with break-out covers are located at the top and bottom.
OPERATING CONDITIONS
Operating conditions: Offices
The distribution board is not intended for outdoor use or in conditions that may have a negative influence on its function and that of the installed components (e.g. environment with risk of explosion or damp and wet rooms).
It must be protected against: mechanical damage
improper handling
use other than that for which the distributor is intended.
Improper treatment means in particular: overloading (exceeding the recommended maximum load)
installation of equipment that may negatively affect the operation and functioning of the manifold or the installed components
tampering with the manifold construction and its design
INSTALLATION OF THE DISTRIBUTION BOARD: In order to guarantee the recommended maximum load, the load must be evenly distributed.
The distribution board must be placed on a level surface, any small unevenness can be compensated with the levelling feet.
In case cables are inserted through one of the openings, they can be sealed with the brush strip (which is part of the accessory pack) or the plastic frame.
ENVIRONMENTAL PROTECTION
All parts are made of recyclable materials. They are to be disposed of in accordance with the applicable regulations after the distributor has been taken out of service.