The cabinet height is specified without the levelling feet supplied in the accessories pack. If these feet are mounted, the installation dimension of the cabinet is increased by 24 to 35 mm.
Door height
1800mm
Rear panel/door
Solid sheet metal rear panel, bolted
Depth
1000mm
Colour
Grey (RAL7035)
Height unit
42U
Front door
Glass door left hinge
Locking of rear door
bolted, without lock
Width
600mm
Protection class
IP54
Side panel right
Solid sheet metal, bolted
Recommended maximum load
800kg
Locking of front door
Multi-point locking with safety lock
Door width
487mm
Detachable rear panel
Detachable side panels
Demountable
Welded standing cabinet with removable walls, for the installation of air-conditioning units, IP54, load capacity 800 kg
Cable inlets
Cable inlet in the roof and floor 300 x 100 mm with sealed cover. In the accessory pack of the manifold is a multiple cable entry with increased degree of protection.
Ceiling trim
The large roof trim enables the installation of an air-conditioning unit with orientation of the air flow according to the needs of the installed components. The installation of an air-conditioning unit reduces the degree of protection of the entire unit to IP20.
IP54 manifoldThe manifolds of the RIE range with increased degree of protection are designed for the protection of the components especially from the harmful effects of water and dust. The roof perforation is only design and does not reduce the tightness. The side panels are fixed to the frame with screws and, like the doors, have a foam seal. They have openings for baying cabinets.
Multi-point closure
The bar closure enables a perfect seal of the door against the cabinet frame. The system is compatible with the handles and locks of leading manufacturers on the world market, including electronic and code locks.
Adjustable vertical latching rails
Complement the two pairs of infinitely adjustable 48,3 cm ( 19 inch ) rails with a third central pair for cabinets deeper than 800 mm.
Sealing, earthing
Triron uses a 3D robot for gluing in the glass and applying the foam seal. All removable cabinet parts are connected to each other Central M8 earthing point on the rear wall. Markings for adjusting the vertical latching rails on the support rails facilitate installation.48,3 cm ( 19 inch ) standing cabinet with IP54 protection
Component of the standing cabinet are 4 adjustable vertical latching rails (6 in cabinets deeper than 800 mm).
Distributor construction: Welded steel frame with removable screwed walls, single-leaf door with foam seal in the versions as solid sheet or glass door with 4 mm thick tempered safety glass. They can be mounted at the front or rear of the cabinet. In order to achieve the necessary tightness, they have a multi-point locking system as standard.
The permissible load capacity of the individual doors is max. 20 kg.
These cabinets are intended for the installation of data and telecommunication systems and their distribution systems.
The distribution frame as well as all removable parts (side and rear panels, doors, . ...) are connected with earthing cables, which must be properly fixed and plugged in during the entire service life of the cabinet.
In the bottom of the distribution board there is an M8 screw as the main earthing point.
Cable entries with break-out covers are located at the top and bottom.