Further information for Theben 2080530 theRonda S360 Slave UP WH Presence Detector White
General
Detection range
4 m (seated persons), 8 m (walking persons) at 3 m mounting height
Mounting height
up to 4 m
Operating voltage
110-230 V AC
Frequency
50/60 Hz
Degree of protection
IP 54
Colour housing
White
Sensitivity
Adjustable
Remote operation
The theRonda S360 Slave UP WH from Theben is an UP presence detector for ceiling mounting, specifically designed to extend the detection range of a master device within a presence control system. The device enables automatic detection of movements in indoor spaces and allows intelligent control of lighting or heating by detecting the presence of people. The housing is white and intended for ceiling mounting, with a maximum mounting height of 4 metres.
Applications
This detector is suitable for indoor use, particularly in offices, corridors, waiting areas, or other rooms where automatic presence detection is required for controlling lighting or heating systems. It is used in combination with a master device to extend the detection range. At a mounting height of 3 metres, the detection range is 4 metres for seated persons and 8 metres for walking persons. However, the mounting height must not exceed 4 metres to ensure proper functionality.
Functions and Features in Detail
The theRonda S360 Slave UP WH features adjustable sensitivity, which can be adapted according to room geometry and usage. This allows precise adjustment to different environments to avoid false alarms. The device is remotely operable, enabling settings and status queries via external devices such as the theSenda P remote control or the theSenda B incl. holder remote control. These remote controls are available as compatible accessories and allow plug-and-play integration with the detectors.
Technology Explained Simply
The detector operates using infrared technology to detect movements in the room. The operating voltage is between 110 and 230 volts AC at a frequency of 50 or 60 Hz, allowing connection to standard mains voltages in Europe and other regions. The power consumption is 0.1 W, indicating very low energy demand. The protection rating IP 54 ensures protection against dust and splashing water, making the device suitable for indoor use in environments with increased humidity or occasional splashing. The housing is white and designed for ceiling mounting.
Compatibility and Accessories
The detector is designed as a slave device and is used in combination with a master device to extend the detection range. Compatible accessories include the theSenda P remote control and the theSenda B incl. holder remote control, which enable plug-and-play integration with the detectors. Additionally, an AP-frame 110A WH is available as a surface-mount frame for presence detectors, supporting clean ceiling installation.
Mounting and Installation
Mounting is performed on the ceiling, with a maximum height of 4 metres. Installation requires an electrical connection to a mains voltage of 110 to 230 V AC. The exact positioning should be chosen to optimally utilize the detection range, with a mounting height of 3 metres enabling the specified detection range of 4 to 8 metres. The remote control function allows easy commissioning and adjustment of the device after installation.
Operational Advantages
The use of the theRonda S360 Slave UP WH enables efficient and energy-saving control of lighting and heating, as devices are only activated when people are present in the room. The adjustable sensitivity and remote control function increase flexibility and adaptability to different requirements. The low power consumption of 0.1 W contributes to energy efficiency, and the IP 54 protection rating ensures reliable operation even in humid indoor environments.