Further information for Siemens FDCIO361 - input/output blocks (1 input 1 output)
For connecting 1 potential-free contact for reporting technical states (e.g. door or ventilation control) or for triggering an alarm
(e.g. sprinkler alarm). For decentralized control of fire doors, ventilation, air conditioning systems.
1 input for potential-free signaling contact. The input line is monitored for open circuits and short circuits (terminating resistors). The input can be configured for status or alarm messages via the fire alarm control panel. 1 output can be configured as non-monitored - potential-free relay contact (AC 22 V, 2 A) or as monitored - relay contact (DC 30 V, 2 A).
Status display via LED. Power is supplied via C-NET, additional power only required if the output is configured as monitored.
Input/output module including 3 resistors and 2 mounting feet for TS35 top hat rail.