Further information for Siemens 6SL3220-3YE60-0CP0 frequency converter 400 kW
General
Rated power
400 kW
Operating voltage
3AC 380–480 V
Frequency range
47–63 Hz
Degree of protection
IP20
Fieldbus
PROFIBUS-DP
EMC filter
Category C3
Construction size
FSH
Operation temperature
-20 to +60 °C
Ambient temperature
0 to +45 °C
Integrated control panel
IOP-2
DC terminals
Pipe filling mode
Bypass function
The frequency converter SINAMICS G120X from Siemens, type 6SL3220-3YE60-0CP0, is an industrial drive controller for use in water and wastewater treatment plants as well as in building technology/HVAC. It is specifically designed for applications with pumps and fans and offers a rated power of 400 kW. The FSH frame size enables compact integration into enclosures, saving space within the enclosure. The converter features an integrated Intelligent Operator Panel (IOP-2), enabling direct operation and parameterization without requiring additional extensions. The integrated fieldbus function PROFIBUS-DP ensures simple and reliable communication with higher-level control systems.
Applications
The SINAMICS G120X is designed for use in water/wastewater (W/WW) plants as well as in building technology/HVAC. It is particularly suitable for pump and fan drives where precise speed control and energy efficiency are required. Integrated industry-specific functions such as the pipe filling mode and the bypass function support safe and efficient operation in these application areas. The robust construction and operating temperature range of -20 °C to +60 °C make the converter suitable even for demanding environments.
Functions and Equipment in Detail
The converter is equipped with an RFI filter of category C3, ensuring compliance with EMC requirements for industrial applications. It operates with a supply voltage of 3AC 380–480 V ±10/–20 % and a frequency of 47–63 Hz. The rated power of 400 kW is achieved under the conditions of 135 % for 3 seconds, 110 % for 60 seconds, or 100 % for 240 seconds. The integrated DC terminal allows connection of du/dt filters, which is beneficial when used with certain motors or when specific voltage waveform requirements apply.
Technology Explained Simply
The frequency converter converts mains voltage into variable voltage and frequency to control the speed of the connected electric motor. The integrated EMC filtering (category C3) reduces interference in the network and ensures reliable operation in industrial environments. The operating temperature range of -20 °C to +60 °C demonstrates the high robustness of the device, which operates stably even under extreme environmental conditions. The integrated PROFIBUS-DP interface enables communication with PLC systems and higher-level controls, allowing for centralized plant control.
Compatibility and Accessories
The SINAMICS G120X can be combined with various options for commissioning and operation, including the Smart Access Module (SAM) or the Basic Operator Panel (BOP-2). These modules support quick parameterization and commissioning. As accessories, the 6SL3256-0AP00-0JA0 SINAMICS G120 TU and the 6SL3255-0AA00-4HA1 handheld for IOP-2 are available, enabling extended operation and diagnostics. The DC terminals allow connection of du/dt filters, which may be required for certain applications.
Mounting and Installation
The converter is designed in FSH frame size and can be mounted in standard enclosures. Mounting typically occurs on a vertical surface within the enclosure. The integrated protection rating IP20 and UL open Type construction are designed for use in enclosed enclosures. The ambient temperature for operation is 0 to +45 °C, while the converter operates stably at an operating temperature of -20 °C to +60 °C. Installation requires compliance with electrical safety regulations and correct wiring according to the technical documentation.
Operational Advantages
The SINAMICS G120X is characterized by simple selection, ordering, and commissioning. Integrated functions such as IOP-2 and PROFIBUS-DP reduce the complexity of integration into existing plants. The compact design saves space, and the robust construction ensures a long service life. Specific industry functions such as pipe filling mode and bypass function optimize operation in water and building technology plants. Compliance with EMC categories C2 and C1 (optional) ensures reliable operation in sensitive environments.