Siemens 6ES73317PF110AB0, EAN: 4025515072027

Siemens 6ES73317PF110AB0 analog input 8AE thermocouple

Siemens 6ES73317PF110AB0 analog input 8AE thermocouple

Lieske Part No. 121588
Mfg Part No 6ES73317PF110AB0
EAN-Code 4025515072027
Manufacturer Siemens
Here only 1.196,00 EUR
1.423,24 EUR incl. VAT

Further information for Siemens 6ES73317PF110AB0 analog input 8AE thermocouple

General
Operating voltage24 V DC
Input current from L+ (no load)240 mA
Input current from backplane bus 5 V DC100 mA
Power loss3 W
Number of analog inputs8
Supported thermocouple typesB, C, E, J, K, L, N, R, S, T, U, TXK/TXK(L) according to GOST
Temperature compensationinternal, external via compensation socket or Pt100
Maximum cable length (shielded)100 m
Resolution (including sign)16 Bit
Conversion time (up to 4 channels)10 ms
Conversion time (from 5 channels)190 ms
Insulation test500 V DC
Front panel connector40-way
Polarization reversal protectionYes
Immunity (400/60/50 Hz)Yes
Diagnostic information readableYes
SF-LED (group fault)Yes
The Siemens 6ES7331-7PF11-0AB0 is an analog input module of the SIMATIC S7-300 family, specifically designed for capturing temperature values via thermocouples. The module offers eight analog inputs, each configured for connection to thermocouples. It supports thermocouple types B, C, E, J, K, L, N, R, S, T, U, as well as TXK/TXK(L) according to GOST. The inputs are optically galvanically isolated, ensuring high immunity to interference and secure data transmission. The module width is 40 mm, making it suitable for use in standard S7-300 enclosures.

Applications
This module is used in industrial control systems where precise temperature measurements are required, for example in process automation, power generation, or the chemical industry. The ability to support various thermocouple types makes it flexible for use in plants with different temperature measurement conditions. The optical isolation of the inputs protects the control system from disturbances caused by high voltages or electrical overvoltages in the measurement area.

Functions and Equipment in Detail
The module features eight analog inputs exclusively intended for thermocouples. It does not support voltage or current inputs, nor resistance thermometers. Temperature compensation is performed internally, with the option for external compensation via a compensation socket or a Pt100 sensor. The characteristic curve linearization is parameterizable and supports thermocouple types B, E, J, K, L, N, R, S, T, and U. The maximum cable length for shielded cables is 100 meters, enabling flexible installation even over longer distances.

Technology Explained Simply
Measurement is performed using an integrating principle, with a resolution of up to 16 bits (including sign). The conversion time is parameterizable; for up to four channels, the basic conversion time is 10 ms per module, and for five or more channels, it is 190 ms per module. Immunity to mains voltage disturbances is specified for frequencies of 400 Hz, 60 Hz, and 50 Hz. The operating voltage is 24 V DC, with integrated reverse polarity protection. The maximum input voltage for voltage inputs is 75 V DC, with 20 V DC being continuously permissible. The maximum input power is 3 W.

Compatibility and Accessories
The module is designed for use in SIMATIC S7-300 control systems and requires a 40-pin front connector. It is compatible with standard S7-300 backplanes. Diagnostic functions include parameterizable diagnostic alarms and limit value alarms, with diagnostic information being readable. A red SF-LED indicates group faults. Galvanic isolation between channels and the backplane bus is optical and tested at 500 V DC.

Mounting and Installation
The module is installed in the S7-300 enclosure and connected via the 40-pin front connector. Installation takes place in an enclosure, with module dimensions of 40 mm (width), 125 mm (height), and 120 mm (depth). The weight is approximately 272 g. Power supply is via the L+ supply voltage of 24 V DC. The inputs are designed for thermocouples, with cable connections made via shielded cables up to a maximum length of 100 m.

Advantages in Operation
Optical galvanic isolation provides high protection against interference and enables secure data transmission. Parameterizable temperature compensation and characteristic curve linearization increase measurement accuracy. The integrated diagnostic function with LED display allows for quick fault detection. Support for various thermocouple types increases application flexibility. The module width of 40 mm enables compact installation in existing S7-300 systems. The maximum cable length of 100 m allows flexible placement of sensors in the process area.