Further information for Siemens 5WG1141-1AB31 - KNX / DALI Gateway Twin
Communication via KNX with digital electronic ballasts (EVG) with DALI interface
Two DALI outputs with DALI-2 certification according to IEC 62386-101 and 103, to which up to 64 DALI ECGs can be connected via a DALI bus line
Integrated power supply unit for an input voltage of AC 110...240 V, 50/60 Hz or DC 120...240 V to supply power to the gateway electronics and the DALI outputs
Support for ECGs type 0, 1, 2, 3, 4, 5, 6, 7 and 8 according to EN 62386 Edition 1 and Edition 2 (DALI-2)
DALI output voltage approx. 19 V, potential-free and short-circuit-proof
External voltage detection during commissioning to indicate whether there is an incorrect mains voltage at a DALI output
LED display to display operating states and error messages
Button for switching between bus and direct operation
One pair of buttons per DALI output for switching all connected lights on or off together in direct operation
One LED per DALI output for displaying the switching status of all connected lights in direct operation
Configurable behavior in the event of a bus voltage failure (standalone operation)
Control (switching, dimming and setting dimming value) of all connected lights together in broadcast mode
Reporting and display of a lamp and electronic ballast error per lighting group and per DALI participant
One-stage or two-stage timer operation
Integrated scene control for up to 32 scenes
Allocation of the DALI electronic ballasts to the individual groups and with the option of testing the electronic ballasts, groups and scenes using the ETS when commissioning the gateway
Possibility of replacing defective DALI electronic ballasts without software (ETS)
Integrated KNX bus coupler with max. only half the standard bus load (5 mA)
KNX bus connection via bus terminal
Modular device for mounting on a mounting rail TH35 EN 60715