| General |
| Operating voltage | 400 V |
| Rated short-circuit current | 15 kA |
| Number of poles | 3 way |
| Release characteristic | C |
| Nominal current | 3 A |
| Construction type | T=70 mm |
The circuit breaker
5SY7303-7 from Siemens belongs to the SENTRON series and is designed for safe short-circuit and overload protection in electrical installations. It is available in 3-pole configuration and is suitable for applications in residential buildings, utility buildings, and special industrial applications. The device offers an operating voltage of 400 V and a rated short-circuit current of 15 kA, making it suitable for protection functions in medium to high load ranges. The version marked with
C refers to the tripping characteristic, which is suitable for typical consumer installations with moderate load. The rated current is
3 A, making it suitable for smaller consumer groups or specific applications with low current requirements. The form factor
T=70 mm defines the width of the device on the mounting rail, allowing it to be installed in standard installation enclosures with corresponding module width.
Applications
The switch is intended for use in electrical distributions where reliable protection against overload and short-circuit is required. It is used in residential and commercial buildings where protection is needed for individual circuits or small consumer groups. The 3-pole configuration enables protection of three-phase systems, with the protection function acting simultaneously on all three conductors. Use in special industrial applications requires careful planning of loads and protection coordination, with the rated values of the device forming the basis for selection.
Functions and Equipment in Detail
The circuit breaker features a
double-chamber terminal, enabling any combination of conductors and busbars. This simplifies wiring, especially when connecting multiple devices to a busbar. The
rear-mounted busbar allows for easy wiring of the feed-in, making installation in the enclosure more efficient. Mounting and dismounting is tool-free via a
double slider, simplifying installation and maintenance and saving time. The switches are available in various pole numbers, with the 3-pole version being typical for three-phase systems.
Technology Explained Simply
The tripping characteristic
C means that the switch trips within seconds at a current of approximately 5 to 10 times the rated current (here 3 A), which is typical for installations with moderate load. In the event of a short-circuit, i.e., a sudden surge in current, the switch reacts within milliseconds to prevent damage to the installation or consumers. The rated voltage of
400 V corresponds to the standard for three-phase networks in Europe, allowing the switch to be used in typical distribution systems. The rated short-circuit current of
15 kA indicates up to which current strength the switch can safely disconnect without damage.
Compatibility and Accessories
The device is compatible with a unified accessory system for the SENTRON series. Suitable accessories include, among others,
pin busbars in various cross-sections and lengths, such as the 5ST3710 (16 mm², 3-phase) or the 5ST3613-4 (10 mm², 3-pole). Also,
auxiliary switches such as the 5ST3010 (1S+1Ö) or
fault signal switches such as the 5ST3020 can be connected to enable additional functions such as status indication or remote control.
Locking devices such as the 5ST3801 or 5ST3803 are used to secure the switch handle, preventing unintended operation. The use of RCD modules such as the 5SM2332-6KK01 (Type A, 30 mA) is also possible to provide additional residual current protection.
Mounting and Installation
Mounting is tool-free via a double slider inserted into the mounting rail. The width of
T=70 mm corresponds to the standard module size, allowing the switch to be installed in typical installation enclosures with DIN or S-system rails. The rear busbar enables direct connection to the feed-in, simplifying wiring. The double-chamber terminal allows connection of conductors and busbars, providing flexible connection options. Installation takes place in a closed enclosure, with electrical regulations and relevant standards (such as DIN VDE 0100) to be observed.
Advantages in Operation
The switch provides reliable protection with short tripping times for overload and short-circuit. Tool-free mounting and dismounting reduces installation effort and enables quick maintenance. Compatibility with a wide range of accessories allows flexible expansion of functions, such as status indication, remote control, or additional residual current protection. The uniform design of the SENTRON series ensures easy handling and maintenance, even in larger installations with multiple switches.