| General |
| Nominal voltage | 400 V |
| Rated short-circuit current | 10 kA |
| Number of poles | 3 way |
| Switching curve | D |
| Nominal current | 25 A |
| Built-in width | 70 mm |
| Product series | 5SY4 |
| Manufacturer | Siemens |
The circuit breaker
Siemens 5SY4325-8 belongs to the SENTRON 5SY4 product series and is designed for safe short-circuit and overload protection in electrical installations. It is suitable for use in residential buildings, utility buildings, and special industrial applications. The device is 3-pole, has a rated voltage of 400 V and a rated short-circuit current of 10 kA. The tripping curve is of type
D, which allows for a high tripping current threshold for installations with high inrush currents, such as motors. The rated current is
25 A, and the mounting width is
70 mm. Mounting is tool-free via a double slider, simplifying installation and removal. The terminals are designed as double-chamber terminals, allowing any combination of conductors and busbars. Power supply can be via a rear-mounted busbar, simplifying wiring.
Applications
The circuit breaker 5SY4325-8 is intended for use in electrical distributions within the field of building electrics and in special industrial installations. It protects wiring and devices against overload and short-circuit. The 3-pole design makes it particularly suitable for 3-phase networks. The D tripping curve is typical for installations with high inrush currents, such as electric drives or transformer installations. The mounting width of 70 mm allows for flexible placement in standard distribution boards.
Functions and Equipment in Detail
The device features a double-chamber terminal, enabling flexible connection of conductors and busbars. The rear busbar simplifies wiring for power supply. Tool-free mounting via a double slider reduces installation time and increases safety during mounting. The tripping curve
D ensures that the breaker does not trip unintentionally during short-term current surges, such as those occurring with motors or other inductive loads. The rated voltage of
400 V and the rated short-circuit current of
10 kA provide sufficient protection performance for typical applications in building and industrial electrics.
Technology Explained Simply
The circuit breaker 5SY4325-8 combines thermal and magnetic tripping mechanisms. The thermal part responds to sustained overload, while the magnetic part trips quickly during sudden short-circuits. The tripping curve
D is designed for loads with high inrush currents, so the breaker does not trip during short-term current surges. The rated voltage
400 V corresponds to the standard in 3-phase networks in Germany. The rated short-circuit current of
10 kA is sufficient for many applications in residential and industrial installations. The mounting width of
70 mm matches the standard for modular devices in distribution boards.
Compatibility and Accessories
Accessories for the 5SY series are standardized and can be combined with all devices in this product line. Available accessories include RCD modules, pin busbars in various cross-sections (e.g. 10 mm², 16 mm²) and configurations (3-phase, 2x3-phase, 3x3-phase), isolating devices, auxiliary switches, under-voltage release units, overload release units, and auxiliary/error signal switches. The pin busbars are designed for safe touch protection and are available in various lengths and cross-sections. RCD modules are available for various current ratings and types (e.g. Type A, selective, 30 mA, 1000 mA). Isolating devices enable safe disconnection and identification of the switch.
Mounting and Installation
Mounting is tool-free via a double slider, which is inserted into the distribution board. The mounting width of 70 mm corresponds to the standard for modular devices. The double-chamber terminal allows flexible connection of conductors and busbars. The rear busbar simplifies wiring for power supply. Installation is carried out in standard distribution boards for modular devices. The devices are intended for use in enclosed distribution boards.
Operational Advantages
The circuit breaker 5SY4325-8 provides reliable protection for electrical installations. Tool-free mounting and removal reduce installation time and increase safety. The flexible combination of conductors and busbars via the double-chamber terminal simplifies wiring. The D tripping curve ensures stable operation with loads having high inrush currents. The standardized accessories for the entire 5SY series enable flexible expansion and maintenance of the installation. The rated voltage of 400 V and the rated short-circuit current of 10 kA meet the requirements of many applications in residential and industrial electrics.