| General |
| Degree of protection | SIGRES |
| Earth fault trip current | 300 mA |
| Nominal current | 25 A |
| Operating voltage | 400 V AC |
| Switch type | B |
| Tripping characteristic | Short-time delayed |
| Number of poles | 4 |
| Connection configuration | 3+N-pole |
| Mounting method | DIN rail (top hat rail) |
| Actuation | slider manual operation |
| Accessory compatibility | SENTRON system kit |
The Siemens residual current circuit breaker type 5SV3642-4 is a 4-pole RCD of the SENTRON series, designed for the protection of persons and property against electric shock. It features a rated current of 25 A and a residual current trip value of 300 mA, with an operating voltage of 400 V AC. The switch is type B and has a short-time delayed tripping characteristic, making it suitable for applications with pulsating or non-sinusoidal fault currents. The device is designed for mounting on a DIN rail and features a slider-hand operation, enabling tool-free removal from the busbar system.
Residual current circuit breakers are electrical switching devices that automatically interrupt the circuit when a dangerous fault current (e.g., due to contact with a conductive part) is detected. The
type B is specifically designed for installations with non-sinusoidal fault currents, such as those occurring with LED lighting, frequency converters, or electronic devices. The
short-time delayed tripping ensures that the switch does not trip during brief, non-hazardous fault currents, but only during sustained, dangerous currents. This prevents unnecessary shutdowns and increases the reliability of the protection system.
Protection rating and environmental conditions are crucial for safe operation. The switch is designed for difficult environmental conditions, indicated by the SIGRES marking (Special Installation Conditions for Residual Current Devices). This includes, among other things, an extended test interval to ensure reliability under demanding conditions. The integrated encircling and shock protection provides additional safety during installation and maintenance by preventing contact with live parts.
Technology explained simply: The SENTRON 5SV3 switch series is modular in design and allows expansion with various functions via a comprehensive accessory system. The slider-hand operation enables easy and safe mounting and removal without tools. The DataMatrix code on the device provides quick access to technical data via the Siemens Industry Online Support App, simplifying maintenance and documentation.
Compatibility and accessories: The device can be extended with various accessories from the Siemens system kit. Examples include auxiliary switches such as the 5ST3062, designed as a changeover switch for AC 230/400 V and DC 24–220 V, or the 5ST3010 as an auxiliary switch with 1 normally closed contact and 1 normally open contact. Other components include pin busbars such as the 5ST3770-4 (10 mm², 4-phase, cuttable, RCD 4P N right) or the 5ST3770-5 (16 mm², 16 TE, 4-phase, cuttable, RCD 4P N right). Additionally, terminal cover caps such as the 5SW3005 (IP40, grey, for surface mounting) and spacers such as the 5TG8240 (0.5 TE, for modular devices T=70 mm) are available. Combining these components enables flexible and application-specific installation.
Mounting and installation: The switch is mounted on a DIN rail, with the slider-hand operation enabling tool-free removal. Installation takes place in a distribution box or N-distribution unit, with the use of intermediate frames such as the 8GB4562 (SIMBOX 63, for 2 devices) or the 8GB4563 (SIMBOX 63, 3-R for 70 mm devices) facilitating integration into existing systems. The connection terminals are designed for secure and reliable connections, with the 3+N-pole configuration allowing separate switching of the neutral conductor.
Operational advantages: The combination of high safety, modular expandability, and tool-free mounting makes the 5SV3642-4 a reliable protection device for industrial and commercial applications. The SIGRES approval for difficult environmental conditions and the extended test interval increase operational safety. Integration into the SENTRON system allows flexible adaptation to specific requirements through the accessory range.