| General |
| Degree of protection | Type A - |
| Earth fault trip current | 30 mA |
| Switching power | 6 kA |
| Nominal current | 10 A |
| Operating voltage | 230 V AC |
| Protection characteristic | C - |
| Model | 1P+N - |
| Certification | DIN EN 61009-1, DIN EN 61009-2-1 - |
| Built-in width | 70 mm |
| Terminal type | Double chamber terminals - |
| System compatibility | SENTRON - |
| Accessory compatibility | 5ST3 pin busbars, 5ST3020, 5ST3062, 5ST3801, 5ST3073, 5ST3030, 5ST3010, 5ST3053, 5SM6021, 5ST3040, 5ST3736, 5ST3612, 5SW3004, 8WH8210, 5ST3640, 5ST3607, 5SW3005, 5ST3608, 5ST3606, 8GB4561 - |
The Siemens FI/LS switch type 5SU1356-7KK10 is a combined protection switch for use in electrical distributions, providing protection against overload, short circuit, and fault currents. It belongs to the SENTRON series and is designed as an RCBO (Residual Current Circuit Breaker with Overcurrent protection). The device is designed for installation in row distributors and offers protection at a fault current of 30 mA, with protection type A enabling detection of pulsating fault currents. The rated current is 10 A, the switching capacity is 6 kA, and the operating voltage is 230 V AC. The protection characteristic is C, indicating medium sensitivity for overload tripping. The 1P+N configuration means the switch disconnects both the phase conductor and the neutral conductor.
Applications
The FI/LS switch is suitable for use in residential and commercial buildings where high safety standards for electrical installations are required. It is particularly installed in distribution enclosures and flush-mounted distribution boxes, where it provides protection functions for individual circuits. Applications are in networks with a nominal voltage of 230 V AC, typically in single- and multi-family homes as well as small commercial enterprises. The protection type A also makes it suitable for installations with electronic devices that may generate pulsating fault currents.
Functions and Equipment in Detail
The device features double-chamber terminals, facilitating the connection of conductors with different cross-sections. This enables flexible wiring without additional tools or adapters. The terminals are designed to ensure a secure and durable contact. The switches are VDE-tested and certified according to DIN EN 61009-1 and DIN EN 61009-2-1, confirming compliance with European safety and performance standards. A Data Matrix code on the device allows quick access to technical data via the Siemens Industry Online Support App.
Technology Explained Simply
The FI/LS switch combines the functions of a circuit breaker (LS) and a residual current circuit breaker (FI). When a fault current of 30 mA or more occurs, the circuit is disconnected within milliseconds to prevent electrical hazards. The C characteristic ensures the switch does not trip prematurely under normal overloads, but only reacts at higher loads, increasing reliability. The switching capacity of 6 kA guarantees that the switch can safely disconnect even under high short-circuit currents.
Compatibility and Accessories
The switch is part of the SENTRON system and can be extended with various accessories. These include, for example, auxiliary switches, fault signal switches, remote actuators, and lockout devices. Connection to other SENTRON devices is achieved via pin busbars of series 5ST3, enabling quick and secure wiring. Compatibility with accessories such as the 5ST3020 fault signal switch or the 5ST3062 auxiliary switch extends the device’s functionality, for example for remote control or status indication.
Installation and Mounting
The switch is designed for installation in standard row distributors and is inserted into the corresponding mounting openings. Mounting requires no additional tools, as the terminals are directly attached to the conductors. The mounting width is 70 mm, matching the standard width for single switches. Installation is carried out in accordance with applicable VDE regulations and the device’s technical specifications.
Operational Advantages
Using the FI/LS switch provides high safety through the combination of overload and fault current protection. The double-chamber terminals simplify installation and ensure reliable connections. Certification according to DIN EN 61009-1 and DIN EN 61009-2-1 ensures compliance with European standards. Integration into the SENTRON system allows flexible expansion with accessories, facilitating adaptation to specific requirements. Using the Siemens Industry Online Support App via the Data Matrix code provides quick access to technical information.