| General |
| Degree of protection | Type A |
| Earth fault trip current | 30 mA |
| Switching power | 6 kA |
| Nominal voltage | 230 V AC |
| Nominal current | 6 A |
| Characteristic | C |
| Number of poles | 1P+N |
| Accessory compatibility | 5ST3 series, remote actuators, auxiliary switches, trip units |
| System | SENTRON |
| Certification | DIN EN 61009-1, DIN EN 61009-2-1 |
| Built-in width | 70 mm |
The Siemens FI/LS switch type 5SU1356-7KK06 is a combined protection switch for use in electrical installations. It combines the functions of a residual current circuit breaker (FI) and a line protection switch (LS) in one device and provides protection against overload, short circuit, and dangerous fault currents. The device is part of the SENTRON series and complies with standards DIN EN 61009-1 and DIN EN 61009-2-1. It is VDE-tested and certified, confirming compliance with safety requirements for use in residential and commercial buildings.
Applications
The FI/LS switch is designed for use in single-phase networks with a nominal voltage of 230 V AC. It is particularly suitable for protection applications in rooms with increased moisture risk, such as bathrooms or kitchens, as well as in areas where high electrical safety is required. The type designation A indicates that the switch also responds to pulsating fault currents, making it suitable for applications with electronic devices.
Functions and features in detail
The switch provides a nominal current of 6 A and a fault current tripping value of 30 mA. The C-characteristic ensures sufficient tripping delay for short-term current surges, preventing disconnection during normal load fluctuations. The switching capacity is 6 kA, indicating the device’s ability to safely interrupt a short circuit. The double-chamber terminals allow easy connection of conductors with different cross-sections, simplifying installation in existing systems.
Technology explained simply
The FI/LS switch operates on the principle of an RCBO (Residual Current Breaker with Overcurrent Protection). It continuously monitors the current flow in the circuit and trips when an imbalance between incoming and outgoing current is detected — an indicator of a fault current. At the same time, it protects against overload and short circuit by automatically disconnecting when current values become too high. The Type A protection ensures response to pulsating fault currents, which can occur in devices with rectifier or electronic power supplies.
Compatibility and accessories
The device is part of the Siemens SENTRON system and can be extended with various accessories. These include, for example, remote actuators such as the 5ST3053 or 5ST3073-0MC, auxiliary switches such as the 5ST3062, as well as load and undervoltage release mechanisms. Connection to other SENTRON devices is achieved via pin busbars of the 5ST3 series, enabling quick and secure parallel connections. Installation is carried out in standard installation switchboards with a depth of 70 mm.
Installation and mounting
The switch is mounted in row-mounted installation devices and is designed for front mounting in switchboards. The terminals are designed for connecting conductors of different cross-sections, enabling flexible use in various installation scenarios. Mounting is done without additional tools, with the mounting width and depth conforming to standards for row-mounted devices.
Operational advantages
By combining FI and LS functions in a single device, the number of required switching devices is reduced, simplifying installation and reducing space requirements. VDE certification and compliance with DIN EN 61009 standards ensure reliable and safe operation. The integrated Data Matrix Code function allows quick access to technical data via the Siemens Industry Online Support App, facilitating maintenance and documentation. The Type A protection expands application possibilities in modern electrical installations with electronic consumers.