| General |
| Degree of protection | Type A |
| Earth fault trip current | 30 mA |
| Short-circuit current trip value | 6 kA |
| Nominal current | 13 A |
| Nominal voltage | 230 V AC |
| Protection characteristic | B |
| Number of poles | 1P+N |
| Built-in width | 70 mm |
| Certification | DIN EN 61009-1, DIN EN 61009-2-1 |
| Product type | Earth leakage circuit breaker |
| Manufacturer | Siemens |
| Series | SENTRON 5SU1 |
The Siemens FI/LS switch type 5SU1356-6KK13 is a combined protection switch for use in electrical installations, providing protection against overloads, short circuits, and earth leakage currents. It belongs to the SENTRON series and is designed as an RCBO (Residual Current Breaker with Overcurrent). The device is intended for installation in row or installation enclosures and offers protection for 1P+N installations with a rated voltage of 230 V AC. It is designed for a rated current of 13 A and features a B characteristic, suitable for general consumer applications. The Type A protection class enables detection of pulsating earth leakage currents, which is particularly important for devices with electronic power supplies. The switch is rated for an earth leakage current of 30 mA and provides a short-circuit trip rating of 6 kA.
Applications
The FI/LS switch is used in residential and commercial buildings where high safety standards for power supply are required. It is especially suitable for installations operating electronic devices with pulsating earth leakage currents, such as PC systems, LED lighting, or household appliances with frequency converters. The combination of earth leakage and circuit protection in a single device reduces the number of required components and simplifies installation. The Type A protection class ensures that non-sinusoidal earth leakage currents are also detected, enhancing safety.
Functions and Equipment in Detail
The switch features double-chamber terminals, enabling simple and secure connection of conductors with different cross-sections. This simplifies installation and reduces mounting time. The terminals are designed to ensure a secure contact even with different conductor cross-sections. The switches are marked with a Data Matrix code, allowing technical data to be accessed directly via the Siemens Industry Online Support app. This supports maintenance and documentation of the installation.
Technology Explained Simply
The FI/LS switch operates on the principle of a residual current device (RCD) and a circuit breaker (LS). It continuously monitors the current flow in the live and neutral conductors. If a difference of more than 30 mA is detected, indicating an earth leakage current, the switch trips within milliseconds. The B characteristic ensures that the switch does not unnecessarily trip during overloads with a slow current rise (e.g., with motors), but only reacts when the rated current is exceeded by a specific amount. The Type A protection class also detects pulsating earth leakage currents, which can occur in devices with rectifiers or frequency converters.
Compatibility and Accessories
The switch is part of the SENTRON system and can be extended with various accessories. These include, for example, overload release units, remote control actuators, auxiliary switches, undervoltage release units, and pin busbars from the 5ST3 series. The pin busbars enable quick and secure connection of multiple protection switches. Additionally, isolation devices, fire protection switch blocks, and handle connectors can be used to enhance the functionality and safety of the installation. Compatibility with the Siemens system building kit ensures modular expansion of the control panel.
Mounting and Installation
The FI/LS switch is designed for mounting in standard installation enclosures. The mounting width is 70 mm, matching the standard width for single switches. The double-chamber terminals simplify the connection of conductors with different cross-sections. Mounting is done by simply snapping the switch into the control panel, with the terminals directly attached to the conductors. The use of pin busbars allows parallel connection of multiple switches, speeding up installation.
Operational Advantages
The combined protection of earth leakage and circuit protection in a single device reduces the number of required components and simplifies planning and installation. The B characteristic ensures reliable protection for general consumers, while the Type A protection class provides additional safety for modern electronic devices. The double-chamber terminals allow flexible and secure connection of conductors with different cross-sections. Integration into the SENTRON system enables modular expansion of the installation with various accessories.